Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04513 Electrical Rough-In1/5/20061/5/20061/5/2006 4:51:52 PMPPART
Scheduled by a contractor via Hello! on 1/5/2006 at 10:48:56 AM. ok to cover u/g to canopy area, need to see before pour in island area
ELE05-04467 Electrical Rough-In1/5/20061/5/20061/5/2006 4:04:44 PMPPART
underground- todd; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie u/g fom bldg east to light pole, and so toward chinden ok to cover
ELE06-00019 Permanent Service1/5/20061/5/20061/5/2006 2:27:53 PMPPASS
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s, o/h, reconnect to new mast, ok
ELE05-04266 Final1/4/20061/5/20061/5/2006 1:34:10 PMPFAIL
steve; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called, left message, left corr notice, 210.12(B) bedroom shall be protected by afci, 408.4 circuit directory shall be complete and concise
ELE06-00029 Final1/5/20061/5/20061/5/2006 1:32:23 PMPPASS
TOBY TEMP POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, t/s u/g n ok
ELE05-04509 Final1/5/20061/5/20061/5/2006 12:53:45 PMPNR
Final Inspection Kelly Tarter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson met elect, needs to do ltr
ELE05-04513 Conference1/4/20061/5/20061/5/2006 11:35:27 AMADONE
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked about u/g for gates, looked at equip listings
ELE05-01642 ELE-Aging Inspection1/5/20061/5/20061/5/2006 10:31:55 AM NR
talked to contr
ELE06-00035 Temporary Service1/4/20061/5/20061/5/2006 10:15:42 AMAFAIL
bruce or office at ###-####; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice,408.7 unused openings for breakers shall be closed,110.12(A) unused cable and ko openings shall be closed, 310.16 #10 conductir shall not be protected by 200a fuses,therefore disconnect from system,450.3(B) pri xfmr protection shall be 125% .
ELE05-04164 Final1/4/20061/5/20061/5/2006 10:11:25 AMAPASS
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
ELE06-00033 Rough-In Permanent Service1/4/20061/5/20061/5/2006 9:40:13 AMAPASS
brandon ###-#### ric ok, p/s u/g n ok
ELE06-00037 Temporary Service1/4/20061/5/20061/5/2006 8:47:13 AMAPASS
please call if you have any questions.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil t/s u/g n ok
ELE06-00039 Temporary Service1/4/20061/5/20061/5/2006 8:46:34 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Shane Vigil t/s u/g n ok
ELE06-00038 Temporary Service1/4/20061/5/20061/5/2006 8:46:08 AMAPASS
Please call me if you have any questions.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil called contr and told he must put on job id stickers. t/s u/g n ok
ELE06-00030 Electrical Rough-In1/4/20061/5/20061/5/2006 8:23:09 AMAPASS
Scheduled by a contractor via Hello! on 1/4/2006 at 3:24:48 PM. Contact: ###-####. ric ok, p/s u/g n ok
ELE05-01626 ELE-Aging Inspection1/5/20061/5/20061/5/2006 8:13:17 AM DONE
see final
ELE04-02698 Final1/5/20061/5/20061/5/2006 12:00:00 AMAPASS
ok to final
ELE05-01626 Final1/5/20061/5/20061/5/2006 12:00:00 AMAPASS
ok to final