ELE05-04513
| Electrical Rough-In | 1/5/2006 | 1/5/2006 | 1/5/2006 4:51:52 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 1/5/2006 at 10:48:56 AM. ok to cover u/g to canopy area, need to see before pour in island area
|
ELE05-04467
| Electrical Rough-In | 1/5/2006 | 1/5/2006 | 1/5/2006 4:04:44 PM | P | PART |
|
|
underground- todd; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie u/g fom bldg east to light pole, and so toward chinden ok to cover
|
ELE06-00019
| Permanent Service | 1/5/2006 | 1/5/2006 | 1/5/2006 2:27:53 PM | P | PASS |
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s, o/h, reconnect to new mast, ok
|
ELE05-04266
| Final | 1/4/2006 | 1/5/2006 | 1/5/2006 1:34:10 PM | P | FAIL |
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called, left message, left corr notice, 210.12(B) bedroom shall be protected by afci, 408.4 circuit directory shall be complete and concise
|
ELE06-00029
| Final | 1/5/2006 | 1/5/2006 | 1/5/2006 1:32:23 PM | P | PASS |
|
|
TOBY TEMP POWER POLE; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contr, t/s u/g n ok
|
ELE05-04509
| Final | 1/5/2006 | 1/5/2006 | 1/5/2006 12:53:45 PM | P | NR |
|
|
Final Inspection Kelly Tarter ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson met elect, needs to do ltr
|
ELE05-04513
| Conference | 1/4/2006 | 1/5/2006 | 1/5/2006 11:35:27 AM | A | DONE |
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked about u/g for gates, looked at equip listings
|
ELE05-01642
| ELE-Aging Inspection | 1/5/2006 | 1/5/2006 | 1/5/2006 10:31:55 AM | | NR |
|
|
talked to contr
|
ELE06-00035
| Temporary Service | 1/4/2006 | 1/5/2006 | 1/5/2006 10:15:42 AM | A | FAIL |
|
|
bruce or office at ###-####; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, left corr notice,408.7 unused openings for breakers shall be closed,110.12(A) unused cable and ko openings shall be closed, 310.16 #10 conductir shall not be protected by 200a fuses,therefore disconnect from system,450.3(B) pri xfmr protection shall be 125% .
|
ELE05-04164
| Final | 1/4/2006 | 1/5/2006 | 1/5/2006 10:11:25 AM | A | PASS |
|
|
MIKE; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
ELE06-00033
| Rough-In Permanent Service | 1/4/2006 | 1/5/2006 | 1/5/2006 9:40:13 AM | A | PASS |
|
|
brandon ###-#### ric ok, p/s u/g n ok
|
ELE06-00037
| Temporary Service | 1/4/2006 | 1/5/2006 | 1/5/2006 8:47:13 AM | A | PASS |
|
|
please call if you have any questions.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil t/s u/g n ok
|
ELE06-00039
| Temporary Service | 1/4/2006 | 1/5/2006 | 1/5/2006 8:46:34 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Shane Vigil t/s u/g n ok
|
ELE06-00038
| Temporary Service | 1/4/2006 | 1/5/2006 | 1/5/2006 8:46:08 AM | A | PASS |
|
|
Please call me if you have any questions.; Phone #: ###-#### Internet Inspection Request from: Shane Vigil called contr and told he must put on job id stickers. t/s u/g n ok
|
ELE06-00030
| Electrical Rough-In | 1/4/2006 | 1/5/2006 | 1/5/2006 8:23:09 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/4/2006 at 3:24:48 PM. Contact: ###-####. ric ok, p/s u/g n ok
|
ELE05-01626
| ELE-Aging Inspection | 1/5/2006 | 1/5/2006 | 1/5/2006 8:13:17 AM | | DONE |
|
|
see final
|
ELE04-02698
| Final | 1/5/2006 | 1/5/2006 | 1/5/2006 12:00:00 AM | A | PASS |
|
|
ok to final
|
ELE05-01626
| Final | 1/5/2006 | 1/5/2006 | 1/5/2006 12:00:00 AM | A | PASS |
|
|
ok to final
|