FIR06-00358
| FIR-Aging Inspection | 1/5/2007 | 1/5/2007 | 1/9/2007 1:18:41 PM | | DONE |
|
|
Work in progress.
|
BLD06-01831
| FIRE-Final Inspection | 1/4/2007 | 1/5/2007 | 1/5/2007 4:59:25 PM | A | PART |
|
|
Agreed in conjunction with the structural inspector to allow temporary occupancy pending the replacement of four light fixtures with defective emergency ballasts. Corrections are to be made and verified for completion early next week as discussed.
|
FIR05-00695
| INSP-Alarm Testing | 1/5/2007 | 1/5/2007 | 1/5/2007 4:54:31 PM | P | PART |
|
|
Correction notice items from previous inspectons for guest rooms and common corridors on floors 6 thru 11 have been verified for completion with the exception of HC guest rooms visible notification appliance synchronization.
|
FIR06-00837
| INSP-Sprinkler Rough-in/Hydro | 1/4/2007 | 1/5/2007 | 1/5/2007 2:22:11 PM | A | PART |
|
|
OH install appears satisfactory, final approval pending inspection for spacing at the curtain when complete.
|
FIR06-00653
| INSP-Final Inspection | 1/4/2007 | 1/5/2007 | 1/5/2007 12:48:30 PM | A | PART |
|
|
Inspection for gate 11 passed, final for this permit pending completion of fire sprinkler modifications at gate 14.
|
FIR06-00660
| INSP-Supply line flush | 1/4/2007 | 1/5/2007 | 1/5/2007 12:05:20 PM | A | PART |
|
|
UG supply line flush completed.
|
FIR06-00677
| INSP-Sprinkler Rough-in | 1/4/2007 | 1/5/2007 | 1/5/2007 11:34:35 AM | A | PART |
|
|
Sprinkler rough-in is now approved for cover at the kitchen drop ceiling area.
|
BLD06-02813
| FIRE-Final Inspection | 1/4/2007 | 1/5/2007 | 1/5/2007 11:13:06 AM | A | PASS |
|
|
Previous c/n items are complete, inspection passed.
|
BLD06-03086
| FIRE-Conference | 1/4/2007 | 1/5/2007 | 1/5/2007 10:48:51 AM | A | DONE |
|
|
On site confrence to discuss demo schedule for the remodel area as it affects the existing fire sprinkler system. Contractor agreed to leave the CPVC system in service until such time as the combustible loading and debris within the space are removed, after which time the CPVC system may be isolated to the remodel area only and a fire watch by hospital security is to be implemented until such time as the new sprinkler system piping is installed per permit scope.
|
BLD06-00088
| FIRE-Final Inspection | 1/5/2007 | 1/5/2007 | 1/5/2007 10:19:14 AM | A | PASS |
|
|
Final fire life safety inspection passed, one missing 2nd pc. 401 escutcheon at the SW below the stairs to be installed today.
|
FIR06-00476
| INSP-Final Inspection | 1/4/2007 | 1/5/2007 | 1/5/2007 9:20:03 AM | A | CANC |
|
|
Please call Brian one hour before arriving.
His number is ###-####. Thanks Phone #: ###-#### Inspection cancelled from web by: Stan Beus
|