ESC08-00700
| Random Inspection | 1/5/2009 | 1/5/2009 | 1/5/2009 4:03:12 PM | P | CANC |
|
|
could not see dirt because of snow
|
ELE07-03503
| Final | 1/5/2009 | 1/5/2009 | 1/5/2009 4:01:50 PM | P | PASS |
|
|
dustin Phone #: ###-#### corrections made, ok to final
|
ESC08-00141
| Random Inspection | 1/5/2009 | 1/5/2009 | 1/5/2009 2:59:27 PM | P | PASS |
|
|
looked ok, too much snow to see dirt
|
ESC07-00876
| Random Inspection | 1/5/2009 | 1/5/2009 | 1/5/2009 2:25:00 PM | P | PASS |
|
|
looked ok except snow prevented seeing dirt
|
ESC07-01124
| General Inspection | 1/5/2009 | 1/5/2009 | 1/5/2009 1:31:11 PM | P | PASS |
|
|
looked ok, too much snow to see dirt
|
ELE09-00006
| Rough-In Permanent Service | 1/5/2009 | 1/5/2009 | 1/5/2009 12:42:20 PM | P | PASS |
|
|
Dave Phone #: ###-#### p/s o/h rec ok
|
ELE09-00007
| Permanent Service | 1/5/2009 | 1/5/2009 | 1/5/2009 12:27:06 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams p/s, exst meter pak, n, ok
|
ELE08-02993
| Permanent Service | 1/3/2009 | 1/5/2009 | 1/5/2009 9:04:35 AM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Phil Baker called, lrft correction notice, NEC 240.24(A) center of operating handle shall not be over 6'-7" above floor, 110.26(A)(1) shall provide minimum 3' clear work space in front of breakers, no esc this project
|