Inspections for the day of: Tuesday, January 5, 2010.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01092 ELE-Aging Inspection1/5/20101/5/20101/8/2010 3:47:16 PM DONE
no activity, suc
ELE08-01209 ELE-Aging Inspection1/5/20101/5/20101/7/2010 4:06:47 PM DONE
no activity, see doc expire
ELE09-02248 Electrical Rough-In1/5/20101/5/20101/5/2010 4:04:29 PMPCANC
Trent Phone #: ###-#### wrong permit and address, called number, contractor went to address, but at another location, he will re-call
ESC09-00341 Random Inspection1/5/20101/5/20101/5/2010 4:01:49 PMPPASS
ELE09-01468 Final1/5/20101/5/20101/5/2010 4:00:20 PMPPASS
Butch Phone #: ###-#### met contractor, ok to final, no card to sign
ESC09-00355 General Inspection1/5/20101/5/20101/5/2010 3:17:41 PMPPASS
looked ok
ELE08-01160 ELE-Aging Inspection1/5/20101/5/20101/5/2010 3:13:28 PM DONE
see final, no esc this project
ELE08-01160 Final1/5/20101/5/20101/5/2010 3:13:04 PMPPASS
ok to final, no esc this project
ELE09-01601 Final1/5/20101/5/20101/5/2010 2:51:20 PMPPASS
Please call Rowdy for conference or to have him meet you 45 minutes ahead so he can meet you at the job site. Inspection on work station tables. Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe called, corrections made, ok to final, no esc this project
ELE09-02312 Permanent Service1/5/20101/5/20101/5/2010 1:55:28 PMPPASS
GUY ###-#### p/s u/g n ok, 1 meter only, no esc this project
ELE09-02386 Rough-In Permanent Service1/5/20101/5/20101/5/2010 12:48:25 PMPPASS
Service and house ready for rough-in inspection Phone #: ###-#### Internet Inspection Request from: Kurt Carlson ric ok, p/s u/g n ok
ELE10-00010 Electrical Rough-In1/4/20101/5/20101/5/2010 10:33:30 AMAPASS
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ok to pour concrete encased electrode only, no esc this project
ELE10-00005 Electrical Rough-In1/4/20101/5/20101/5/2010 9:41:28 AMAPASS
Contact: Garrett Collins Phone #: ###-#### Internet Inspection Request from: Deb Gooden walls only ok to cover, no esc this project
ELE10-00003 Electrical Rough-In1/4/20101/5/20101/5/2010 9:08:31 AMAPASS
James Phone #: ###-#### ric ok, see final, no esc this project
ELE10-00003 Final1/5/20101/5/20101/5/2010 9:08:13 AMAPASS
James Phone #: ###-#### ok to final, no esc this project
ELE09-02312 Permanent Service1/4/20101/5/20101/5/2010 8:30:04 AMPFAIL
Guy Phone #: ###-#### met electrican, left correction notice, NEC 110.26(F)(2) outdoor working clearance shall include the zone described in 110.26(A). No appurtances shall be located in this zone, inspection was recalled for pm after 7:30