Inspections for the day of: Monday, January 5, 2015.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GCE15-00001 GCE-Permanent Service1/5/20151/5/20151/5/2015 3:44:28 PMPFAIL
Corey ###-####
110.12(B) Integrity of Electrical Equipment and Connections. Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials.
250.53- Unable to verify grounding electrode system. 2 rods required for permenant service.
*Unable to verify rating of cord from moble home to service
ELE14-03119 Final12/31/20141/5/20151/5/2015 2:59:04 PMPPASS
Kenny Phone #: ###-#### Final ok
ELE14-03242 Electrical Rough-In1/5/20151/5/20151/5/2015 2:28:14 PMPPASS
Partial wall inspection. Call contact before inspection please.
Thank you Phone #: ###-#### Inspection requested via web by Chris Chesnut Walls in lobby area rough in ok cover
ELE14-03364 Final1/5/20151/5/20151/5/2015 1:49:24 PMPFAIL
Final inspection for this property. Contact is Justin Metcalf. Thank you and have a good day. Phone #: ###-#### Inspection requested via web by Laura Longshaw
210.8-Ground fault circuit interupters shall be installed in a readily accessible location.
210.8(B)(5)- Receptical outlets located with in 6' of sink shall have GFCI protection.
400.8- Flexible cordd shall not be ran through holes in walls.
BCC 4-05-32 Code violations not to be retained
314.29- Boxes shall be installed so that the wiring contained in them can be rendered accessible without removing any part of building.
MIS14-00290 ELE-Conference1/5/20151/5/20151/5/2015 9:46:21 AMPCANC
Check for permit for interior of enclosed porch
MIS14-00290 ELE-Conference12/16/20141/5/20151/5/2015 9:42:31 AMANH
Check for permit for interior work Unable to make contact. no answer at door
ELE14-03042 Final1/5/20151/5/20151/5/2015 9:27:12 AMAPASS
call first ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER Final ok
ELE14-03042 Electrical Rough-In1/5/20151/5/20151/5/2015 9:26:45 AMAPASS
call first ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER Mini split rough in ok
ELE14-03562 Final12/31/20141/5/20151/5/2015 9:00:32 AMAPASS
Shannon is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Final ok
ELE14-03562 Electrical Rough-In1/5/20151/5/20151/5/2015 9:00:02 AMPPASS
Shannon is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates Work station recepticals rough in ok