Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01425 ELE-Aging Inspection1/5/20151/5/20151/5/2015 2:08:41 PM DONE
spoke to Andy, almost finished with trim out and will call for final soon.
ELE14-03406 Rough-In Permanent Service1/5/20151/5/20151/5/2015 2:04:46 PMPFAIL
Tim is general contractor. Call if needed and he can contact John if any problems. Inspection is for service only to allow for removal of power off of the house to the garage. New meter is installed on the garage. Phone #: ###-#### Inspection requested via web by John Harvey
110.3 installation and use of equipment, shall be installed in accordance to listing and labeling, ground clamp is loose and wire is not properly clamped
left message
ELE14-02957 Final1/2/20151/5/20151/5/2015 1:44:31 PMPPASS
Please call me when you are on your way so I can let you in. Thanks ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan
Final OK
ELE15-00005 Final1/5/20151/5/20151/5/2015 1:11:15 PMPCANC
call or text hour before// Kevin Phone #: ###-####
wrong inspection, see conf.
ELE15-00005 Conference1/5/20151/5/20151/5/2015 1:10:57 PMPDONE
call or text hour before// Kevin Phone #: ###-####
discussion for PV system, allowance of 65 amp breaker in meter main for PV, based on 225 rated buss. grounding requirements, and inspections needed.
ELE14-03121 Final1/5/20151/5/20151/5/2015 12:57:59 PMPFAIL
Kevin Phone #: ###-####
406.9 all outdoor receptacles shall be listed weather resistant type
110.26A1 space about electrical equipment , 3 ft. clearance in front of panels
240.4 protection of conductors, 12 awg on 30 amp
110.12 unused openings shall be closed
372.13 removal of abandoned outlets required
ELE14-00482 Final1/5/20151/5/20151/5/2015 9:39:08 AMAPASS
call first Phone #: ###-#### Inspection requested via web by PAT MILLER
final OK
ELE14-03003 Final1/5/20151/5/20151/5/2015 9:13:35 AMAPASS
call first Phone #: ###-#### Inspection requested via web by PAT MILLER
Final OK
ELE14-03003 Electrical Rough-In1/5/20151/5/20151/5/2015 9:13:04 AMAPASS
call first Phone #: ###-#### Inspection requested via web by PAT MILLER
lighting retro, misc offices, shop area, exterior, RI OK
ELE14-03515 Rough-In Permanent Service1/2/20151/5/20151/5/2015 8:46:25 AMAPASS
corrections made, ok to cover interior only, no soffit cover allowed, WUI zone.
PS, UG, N, OK