ELE13-01609
| ELE-Aging Inspection | 1/5/2016 | 1/5/2016 | 1/7/2016 1:57:27 PM | | DONE |
|
|
spoke with Seth and he will get this resovlved
|
ELE12-01179
| ELE-Aging Inspection | 1/5/2016 | 1/5/2016 | 1/7/2016 1:53:02 PM | | DONE |
|
|
spoke with Bob and he is following up on this
|
ELE13-00718
| ELE-Aging Inspection | 1/5/2016 | 1/5/2016 | 1/6/2016 8:37:46 AM | | DONE |
|
|
left message for Shawn
|
ELE16-00020
| Permanent Service | 1/4/2016 | 1/5/2016 | 1/5/2016 10:35:18 AM | A | PASS |
|
|
APT. #102 Call manager for access to unlock- ###-#### Phone #: ###-#### Inspection requested via web by Dan Hobdey p/s u/g rec ok meter bank
|
ELE16-00020
| Final | 1/5/2016 | 1/5/2016 | 1/5/2016 10:29:02 AM | P | PASS |
|
|
APT. #102 Call manager for access to unlock- ###-#### Phone #: ###-#### Inspection requested via web by Dan Hobdey final ok
|
ELE15-03021
| Final | 1/4/2016 | 1/5/2016 | 1/5/2016 10:06:55 AM | A | FAIL |
|
|
Lock box code 1049 Phone #: ###-#### Inspection requested via web by Neal Rumsey Dining room receptacle has open ground, 210.12(A) and (B)-all outlets in bedrooms shall be AFCI protected, 250.52(A)(1)- metal underground water pipe shall be bonded to service, 422.31(B)-water heater shall have disconnect in sight or lockoff on breaker, 210.63- a 120 volt receptacle shall be installed within 25 foot of HVAC equipment
|
ELE15-04090
| Final | 1/4/2016 | 1/5/2016 | 1/5/2016 8:45:45 AM | A | PART |
|
|
If you have any questions, please call Clay. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan corrections made final ok on house only. garage not done
|