Inspections for the day of: Thursday, January 5, 2017.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00817 INSP-Final Inspection1/3/20171/5/20171/5/2017 1:20:15 PMPPASS
Final fire alarm communicator inspection passed/complete.
BLD16-02075 FIRE-Final Inspection1/5/20171/5/20171/5/2017 11:38:48 AMPPART
Partial life fire safety inspection complete, final fire sprinkler inspection complete, final fire alarm inspection complete, knox box is in place, fire extinguisher are in place with current inspection tags. Building inspector approved TCO at completion of life fire safety (Items for TCO for life safety complete). A final life fire safety inspection will need to be performed before final occupancy, items that need to be verified for final inspection: final sign off for racking permit BLD16-03887, verify completion of comment 21 under storage issues on the fire plan review comments and fire department access when site work is complete.
BLD16-03887 FIRE-Final Inspection1/5/20171/5/20171/5/2017 11:26:23 AMPPART
Partial final complete for racking permit inspection, final sign off for racking is contingent on the anchor point special inspection.
FIR16-00656 INSP-Final Inspection1/4/20171/5/20171/5/2017 11:24:22 AMAPASS
Final fire alarm inspection passed/complete
FIR16-00535 INSP-Final Inspection1/4/20171/5/20171/5/2017 11:24:01 AMAPASS
Final fire sprinkler inspection passed/complete