Inspections for the day of: Friday, January 5, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00768 INSP-Sprinkler Rough-in/Hydro1/4/20181/5/20181/5/2018 11:25:13 AMAPASS
The overhead rough-in and hydro test passed for the new addition. Contractor will add the branchline restraints before next inspection as discussed.

Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
FIR17-00593 INSP-Sprinkler Rough-in1/5/20181/5/20181/5/2018 11:06:09 AMAPASS
Rough-in passed
FIR17-00631 INSP-Sprinkler Rough-in1/5/20181/5/20181/5/2018 11:05:09 AMAPASS
Rough-in passed. Correctlons have been made at the mezzanine
FIR17-00687 INSP-Sprinkler Rough-in1/5/20181/5/20181/5/2018 11:04:21 AMAPASS
Rough-in passed.
FIR17-00772 INSP-Sprinkler Rough-in1/4/20181/5/20181/5/2018 11:03:32 AMAPART
Rough-in is ok but plans need to be resubmitted showing the change out of all the existing pendant heads to new pendant heads.
FIR17-00320 INSP-Final Inspection1/4/20181/5/20181/5/2018 9:17:40 AMAPASS
Permit finaled
BLD16-04310 FIRE-Final Inspection1/4/20181/5/20181/5/2018 9:14:54 AMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by David Scaggs
FIR17-00499 INSP-Sprinkler Rough-in1/4/20181/5/20181/5/2018 9:03:50 AMAPART
Sprinkler piping in Rooms 200 and 208 is ok to cover but the pendant head in the Electrical Closet is overspaced.

cecil Phone #: ###-####