FIR02-00346
| FIR-Aging Inspection | 1/6/2003 | 1/6/2003 | 1/6/2003 12:00:00 AM | | NR |
|
|
See notes for FIR02- 00253 1/6/2003 12:11:11 PM 1/6/2003 12:11:26 PM
|
BLD02-01971
| FIRE-Final Inspection | 1/2/2003 | 1/6/2003 | 1/6/2003 12:00:00 AM | A | CANC |
|
|
The owner stated that they did not call in for the inspection and they are not ready for an inspection 1/6/2003 12:01:31 PM
|
FIR02-00214
| INSP-Final Inspection | 1/2/2003 | 1/6/2003 | 1/6/2003 12:00:00 AM | A | CANC |
|
|
The bank personel were not on site to give the contractor and I access. Inspection to be rescheduled 1/6/2003 10:26:02 AM
|
BLD02-00692
| FIRE-Final Inspection | 1/3/2003 | 1/6/2003 | 1/6/2003 12:00:00 AM | A | FAIL |
|
|
provide ADA approved hardware on the slider doors, see cabo/ansi A11.7.1 section 4, 404.2.7. Remove thumbturn from north exit door, see cabo/ansi A11.7.1 section 4, 404.2.7. Provide "Door to remain unlocked during business hours" at the main exit door per review note #2. Verify the marking of the medical piping per review note #5. Provide address per review note # 10. Provide fire extinguishers per review note #11. Provide automatic shutdown of the HVAC units per UMC section 608. Remove the manual flush bolt from the double doors near the main exit. See UBC section 1003.3.1.8 1/6/2003 11:31:38 AM
|
BLD02-02651
| FIRE-Final Inspection | 1/5/2003 | 1/6/2003 | 1/6/2003 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 1/6/2003 2:51:20 PM
|
FIR02-00227
| INSP-Final Inspection | 1/2/2003 | 1/6/2003 | 1/6/2003 12:00:00 AM | P | PASS |
|
|
fire sprinkler deficiencies have been corrected. The new tamper switches on the fire pump have been tested 1/6/2003 3:28:32 PM
|
BLD02-00692
| FIRE-Final Inspection | 1/6/2003 | 1/6/2003 | 1/6/2003 12:00:00 AM | P | FAIL |
|
|
###-#### This inspection was set up by the sprinkler contractor but as with the earlier inspection comments I could not verify where the sprinkler tie in is 1/6/2003 4:18:04 PM
|