Inspections for the day of: Thursday, January 6, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Johnson
TitlePLM-INSPECTOR
Phone #794-9476
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM04-03084 Final1/5/20051/6/20051/6/2005 12:00:00 AMAPASS
randall ###-####
PLM05-00008 Water and/or Sewer1/5/20051/6/20051/6/2005 12:00:00 AMANR
PLM05-00009 Water and/or Sewer1/5/20051/6/20051/6/2005 12:00:00 AMAPASS
PLM04-03863 Plumbing Rough-in1/5/20051/6/20051/6/2005 12:00:00 AMAFAIL
Internet Inspection Request from: Kim Alderson test failed on D.W.V. and water talked to plumber on job site will recall when ready 1/6/2005 9:26:16 AM
PLM05-00007 Water and/or Sewer1/6/20051/6/20051/6/2005 12:00:00 AMPPASS
###-#### holly
PLM04-02888 Final1/6/20051/6/20051/6/2005 12:00:00 AMPPASS
pete; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
PLM05-00008 Water and/or Sewer1/6/20051/6/20051/6/2005 12:00:00 AMPPASS
PLM04-03863 Plumbing Rough-in1/6/20051/6/20051/6/2005 12:00:00 AMPFAIL
Reinspection Internet Inspection Request from: Kim Alderson test failed on D.W.V. water test ok contractor to recall when ready 1/6/2005 1:32:54 PM
PLM04-03164 Final1/6/20051/6/20051/6/2005 12:00:00 AMPPASS
gene; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
PLM04-03221 Final1/6/20051/6/20051/6/2005 12:00:00 AMPPASS
gene; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
PLM05-00044 Plumbing Rough-in1/6/20051/6/20051/6/2005 12:00:00 AMPPART
leo- ###-#### need to run softner drain,s in both unit,s and terminate one inch above flood level rim of washer box. correct san tee for vent in down staires bathroom in unit 8537 installed backward,s nail plate above tub in unit 8537 left correction notice contractor to recall when ready 1/6/2005 2:43:21 PM 1/6/2005 2:44:19 PM
PLM04-03155 Plumbing Rough-in1/4/20051/6/20051/6/2005 12:00:00 AMPFAIL
Pete; Phone #: ###-#### Internet Inspection Request from: Jan Rice submit stamped drawing of exiterior installation of premise backflow valve in accorandance with pacific northwest A.W. W, A. cross-connection control manual sixth edition chapter 7 page 10 & 12 or alteranate option : just install backflow premise valve inside building 1/7/2005 10:07:13 AM
PLM04-03134 Plumbing Rough-in1/4/20051/6/20051/6/2005 12:00:00 AMPPART
Pete; Phone #: ###-#### Internet Inspection Request from: Jan Rice roof and overflow drain,s test ok for premise protection rough-in see note under permit # plm04-03155 1/7/2005 10:11:44 AM 1/7/2005 10:12:32 AM
PLM04-03089 Plumbing Rough-in1/4/20051/6/20051/6/2005 12:00:00 AMPPART
Pete; Phone #: ###-#### Internet Inspection Request from: Jan Rice roof and overflow drain,s test ok for premise protection rough-in see note under permit # plm04-03155 1/7/2005 10:10:03 AM 1/7/2005 10:12:08 AM