Inspections for the day of: Friday, January 6, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03243 Final1/6/20061/6/20061/6/2006 3:16:35 PMPPASS
ok survey posted 210.52(G) needs 120 V gfci recept in garage
ELE06-00004 Rough-In Permanent Service1/6/20061/6/20061/6/2006 2:32:06 PMPFAIL
john; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. posted called left message BCC no violatios to be retained, open wiring outlet garage door opener ,110.12 seal unused KOs, 314.16 box fill all areas, 312.5 conn for GEC, 310.8(D) p/s mast wires need to be sunlight resistent,, all single family dwelling is duplex now, p/s boot legged in after I turned it down in 1996 Royal elect service has a/c line and gas line in dedicated space also
ELE05-02538 Electrical Rough-In1/5/20061/6/20061/6/2006 1:02:23 PMPPART
partial ceiling rough-in inspection. Thanks; Phone #: ###-#### Internet Inspection Request from: Steve Syltie high ceiling area ok
ELE05-04255 Final1/6/20061/6/20061/6/2006 12:18:59 PMPNH
Scheduled by a contractor via Hello! on 1/6/2006 at 8:23:29 AM. Contact: ###-####. no access owners son was in accident shop closed called
ELE05-04324 Electrical Rough-In1/5/20061/6/20061/6/2006 10:40:56 AMAPASS
Scheduled by a contractor via Hello! on 1/5/2006 at 3:20:19 PM. Contact: ###-####. ceilings ok
ELE05-04540 Temporary Service1/5/20061/6/20061/6/2006 10:28:17 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook t/s u/g new ok//Temp service insp entered on wrong permit and should be VOIDED, so moved to ele05-04560 eus 2-9-06
ELE05-04497 Electrical Rough-In1/5/20061/6/20061/6/2006 10:10:00 AMAPASS
for soffit cover//adam; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok
ELE06-00034 Conference1/4/20061/6/20061/6/2006 9:25:53 AMADONE
ken -call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
ELE06-00052 Electrical Rough-In1/5/20061/6/20061/6/2006 8:54:07 AMAPART
Scheduled by a contractor via Hello! on 1/5/2006 at 3:54:48 PM. Contact: ###-####. hall , bed rms , and bath rms
ELE05-04560 Temporary Service1/5/20061/6/20061/6/2006 12:00:00 AMPPASS
Insp was requested on the wrong permit ele05-04540 eus 2-9-06