ELE04-00994
| ELE-Aging Inspection | 1/6/2006 | 1/6/2006 | 1/6/2006 6:39:46 PM | | NR |
|
|
called, they will check out
|
ELE05-01666
| ELE-Aging Inspection | 1/6/2006 | 1/6/2006 | 1/6/2006 6:39:08 PM | | DONE |
|
|
see final
|
ELE05-04643
| Temporary Service | 1/6/2006 | 1/6/2006 | 1/6/2006 3:35:33 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/6/2006 at 9:13:12 AM. Contact: ###-####. called contr, left corr notice, 312.5 conductors entering enclosures shall be protected from abrasion
|
ELE05-04509
| Final | 1/6/2006 | 1/6/2006 | 1/6/2006 2:39:19 PM | P | PASS |
|
|
Final inspection Jeff Moe ###-####; Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson no card to sign, called contr, left survey, 406.4 recpts shall be securely fastened in place
|
ELE06-00057
| Electrical Rough-In | 1/5/2006 | 1/6/2006 | 1/6/2006 2:18:22 PM | P | CANC |
|
|
kelly - ###-#### told homeowner that since they did not do the elect work, they need to cancel permit and have Roy K pull elect permit, they need gnds tied together in bathroom switches and 12 gnd for recpt, 1 1/4", and prove 20A ckt for bath recpt. will need panel sched brought up to date.
|
ELE06-00061
| Temporary Service | 1/6/2006 | 1/6/2006 | 1/6/2006 1:31:15 PM | P | PASS |
|
|
bob- ###-#### t/s u/g n ok
|
ELE06-00017
| Final | 1/4/2006 | 1/6/2006 | 1/6/2006 10:24:52 AM | A | PASS |
|
|
We installed and wired 1 new unit heater in the Sun Room along with a disconnect switch for it. We fed it from the existing outdoor panel. Thanks !!!! Dan. ; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok to final
|
ELE05-01667
| ELE-Aging Inspection | 1/6/2006 | 1/6/2006 | 1/6/2006 10:14:55 AM | | DONE |
|
|
see final
|
ELE05-04559
| Electrical Rough-In | 1/5/2006 | 1/6/2006 | 1/6/2006 10:13:18 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 1/5/2006 at 3:27:44 PM. Contact: ###-####. called contr, said need to do am, soffits only in front ok, part wall on left ok to cover
|
ELE06-00035
| Permanent Service | 1/5/2006 | 1/6/2006 | 1/6/2006 9:23:48 AM | A | CANC |
|
|
bruce ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie see t/s
|
ELE05-04426
| Electrical Rough-In | 1/5/2006 | 1/6/2006 | 1/6/2006 8:57:36 AM | A | FAIL |
|
|
ceiling; Phone #: ###-#### Internet Inspection Request from: Jim Williams called cont, left corr notice, 725.3(B) abandoned cables shall be removed, 300.11(A) fixtures shall have 2 independent support wires and identified
|
ELE05-04569
| Electrical Rough-In | 1/5/2006 | 1/6/2006 | 1/6/2006 8:35:39 AM | A | PASS |
|
|
###-#### - seth corr made, ok to cover walls and clg
|
ELE05-03168
| Final | 1/5/2006 | 1/6/2006 | 1/6/2006 8:14:41 AM | A | FAIL |
|
|
Thank you!; Phone #: ###-#### Internet Inspection Request from: William Zerfas called contr, left message, left corr notice, 410.8(D) fixture in closet shall be 12" from point of storage, 430.107 jetted tub disc shall be readily accessible
|
ELE06-00035
| Temporary Service | 1/6/2006 | 1/6/2006 | 1/6/2006 12:00:00 AM | A | PASS |
|
|
bruce ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corr made, t/s o/h, exst, ok
|
ELE05-01667
| Final | 1/6/2006 | 1/6/2006 | 1/6/2006 12:00:00 AM | A | PASS |
|
|
ok to final
|
ELE05-01666
| Final | 1/6/2006 | 1/6/2006 | 1/6/2006 12:00:00 AM | P | PASS |
|
|
ok to final
|
ELE05-04426
| Electrical Rough-In | 1/5/2006 | 1/6/2006 | 1/5/2006 11:44:16 AM | P | CANC |
|
|
ceiling; Phone #: ###-#### Internet Inspection Request from: Jim Williams Inspection cancelled from web by: Jim Williams
|