BLD05-02816
| FIRE-Final Inspection | 1/6/2006 | 1/6/2006 | 1/6/2006 4:02:50 PM | P | NR |
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore The related fire alarm permit must pass inspection prior to life safety final.
|
FIR05-00849
| INSP-Final Inspection | 1/6/2006 | 1/6/2006 | 1/6/2006 4:01:09 PM | P | FAIL |
|
|
Addressing at two smoke detectors does not match between map and panel for correct location, EOL voltage is too low for min. requirements on battery backup, cd rating at one strobe in the open area has been changed from a 60 as shown on approved plans to a 110.
|
BLD05-02317
| FIRE-Final Inspection | 1/5/2006 | 1/6/2006 | 1/6/2006 2:59:44 PM | P | NR |
|
|
Related work including the restrooms and rated exit corridor must be completed per city approved plan and review notes prior to final as indicated on previous correction notice, not ready for final at this time per conversation with Jeff.
|
BLD02-02566
| FIRE-Conference | 1/6/2006 | 1/6/2006 | 1/6/2006 2:24:19 PM | P | DONE |
|
|
On site discussion regarding exiting requirements and door hardware issues.
|
FIR05-00746
| INSP-Sprinkler Rough-in/Hydro | 1/6/2006 | 1/6/2006 | 1/6/2006 1:05:07 PM | P | PART |
|
|
Overhead rough-in is good for cover at the lobby, kitchen, corridor ,confrence and reception areas, two upright heads above drop ceiling at the market room need to be removed as indicated on plans, one upright head in the staff laundry is painted, need to verify enclosed space at the end of meeting room as marked on plans is noncombustible or sprinklered, rotate aux. drain for antifreeze system to the lowest portion of the pipe, provide flex coupling at the top of riser, need to complete seismic bracing.
|
FIR05-00902
| INSP-Final Inspection | 1/5/2006 | 1/6/2006 | 1/6/2006 11:38:26 AM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR05-00851
| INSP-Final Inspection | 1/5/2006 | 1/6/2006 | 1/6/2006 10:54:05 AM | P | PART |
|
|
Overhead sprinkler rough-in is good for cover, will final permit when ceiling tile and escutcheons are installed.
|
BLD05-02662
| FIRE-Final Inspection | 1/5/2006 | 1/6/2006 | 1/6/2006 10:26:30 AM | P | PASS |
|
|
Items on c/n are complete, fire life safety passed inspection.
|
BLD05-01715
| FIRE-Final Inspection | 1/5/2006 | 1/6/2006 | 1/6/2006 10:25:37 AM | P | PASS |
|
|
Items on c/n are complete, fire life safety finaled.
|
FIR05-00778
| INSP-Final Inspection | 1/6/2006 | 1/6/2006 | 1/6/2006 10:23:27 AM | A | PASS |
|
|
Corrections have been made, fire sprinkler finaled.
|
FIR05-00744
| INSP-Final Inspection | 1/6/2006 | 1/6/2006 | 1/6/2006 10:21:31 AM | A | PASS |
|
|
Fire sprinkler demo passed.
|
BLD05-03075
| FIRE-Final Inspection | 1/5/2006 | 1/6/2006 | 1/6/2006 8:50:59 AM | A | PASS |
|
|
Fire life safety is acceptable.
|
FIR05-00848
| INSP-Final Inspection | 1/5/2006 | 1/6/2006 | 1/6/2006 8:47:57 AM | A | PASS |
|
|
Required corrections have been completed, fire alarm permit finaled.
|
FIR05-00868
| INSP-Final Inspection | 1/6/2006 | 1/6/2006 | 1/6/2006 8:46:19 AM | P | PASS |
|
|
The required corrections have been made, fire sprinkler passed inspection.
|