FIR11-00297
| INSP-Final Inspection | 1/6/2012 | 1/6/2012 | 1/6/2012 3:31:44 PM | P | CANC |
|
|
rescheduled for monday
|
BLD11-02030
| FIRE-Conference | 1/6/2012 | 1/6/2012 | 1/6/2012 3:25:00 PM | P | DONE |
|
|
I stopped an electrician from connecting the hood to the fire alarm until a permit has been submitted and issued. I also spoke with one of the owners "Ling" about this issue.
|
FIR11-00686
| INSP-Final Inspection | 1/5/2012 | 1/6/2012 | 1/6/2012 3:24:30 PM | P | CANC |
|
|
Inspection cancelled per Don due to the hood not being connected to the fire alarm system. As a side note I stopped an electrician from connecting the hood to the fire alarm until a permit has been submitted and issued. I also spoke with one of the owners "Ling" about this issue.
|
FIR11-00543
| INSP-Sprinkler Rough-in | 1/6/2012 | 1/6/2012 | 1/6/2012 3:21:15 PM | P | CANC |
|
|
I notified Scott Carter that I was not comfortable continuing with the inspection due to the issues encountered during yesterdays inspection. Again the remote area in question is down to a 5% cushion due to the pipe routing changes already encountered and now there have been additional fitting added that were not shown on the as-builts of the plan modifications. Plans need to be resubmitted that shown ALL pipe routing changes and additional fittings with the accompanying matching hydraulic calculations prior to any more inspections.
|
FIR11-00464
| INSP-Alarm Testing | 1/5/2012 | 1/6/2012 | 1/6/2012 2:22:06 PM | A | CANC |
|
|
Final for alarms Phone #: ###-#### >> Inspection requested via web by John Venche
|
FIR11-00464
| INSP-Final Inspection | 1/5/2012 | 1/6/2012 | 1/6/2012 2:21:55 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by John Venche
|
BLD11-02954
| FIRE-Final Inspection | 1/6/2012 | 1/6/2012 | 1/6/2012 1:39:44 PM | P | PASS |
|
|
life safety passed
|
BLD10-02666
| FIRE-Alarm Testing | 1/5/2012 | 1/6/2012 | 1/6/2012 10:20:43 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Todd Kurns Inspection cancelled from web by: Todd Kurns
|
BLD10-02666
| FIRE-Final Inspection | 1/5/2012 | 1/6/2012 | 1/6/2012 10:20:37 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Todd Kurns Inspection cancelled from web by: Todd Kurns
|
FIR11-00464
| INSP-Alarm Testing | 1/5/2012 | 1/6/2012 | 1/5/2012 4:58:14 PM | A | CANC |
|
|
Final for Fire Alarm Phone #: ###-#### >> Inspection requested via web by John Venche Inspection cancelled from web by: John Venche
|
FIR11-00464
| INSP-Sprinkler Rough-in/Hydro | 1/5/2012 | 1/6/2012 | 1/5/2012 4:57:40 PM | A | CANC |
|
|
FINAL FOR ALARM Phone #: ###-#### >> Inspection requested via web by John Venche Inspection cancelled from web by: John Venche
|