Inspections for the day of: Tuesday, January 6, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-00023 Electrical Rough-In1/6/20151/6/20151/6/2015 2:57:17 PMPPASS
Wall rough-in inspection - contact is Robert Gates ###-#### Phone #: ###-#### Inspection requested via web by Scott Campbell Asked what type of fluid would be present, not sure at wall rough in time but believe no hazardous location should be present, working with plastics. Offices, panel shop, break room, pipe assembly room, compressor room, and plastic assembly room wall rough in ok cover.
ELE14-03322 Final1/6/20151/6/20151/6/2015 2:19:12 PMPPASS
Phone #: 6299948 >> Inspection requested via mobile web by David McClellan Final ok
ELE14-03559 Final1/6/20151/6/20151/6/2015 1:48:30 PMPCANC
Phone #: ###-#### Inspection requested via web by daniel bibikov Needed rough in permanant service inspection
ELE14-03559 Rough-In Permanent Service1/6/20151/6/20151/6/2015 1:48:16 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
ELE14-03236 Final1/6/20151/6/20151/6/2015 1:46:56 PMPNR
Phone #: ###-#### Inspection requested via web by daniel bibikov Have not started trimming units yet.
ELE15-00020 Rough-In Permanent Service1/6/20151/6/20151/6/2015 1:05:48 PMPFAIL
Contact Ben if any questions Phone #: ###-#### Inspection requested via web by Ben Archibald 210.52(G)(1)- Each garage space shall have a receptacle outlet installed for that space that shall be fed by a dedicated circuit that shall feed no other outlets.
300.4- Where bored holes are less than 1 1/4" from framing surface NM cable shall be protected from physical damage.
300.4(D)- NM cable shall not be secured less than 1 1/4" from framing surface. Stapling side by side on 2x4 studs.
334.40(A)- NM cable shall terminated in a box. entry christmas.
590.6(B)- Receptacle temporary outlets other than 120 volt shall have GFCI protection
ELE15-00017 Final1/5/20151/6/20151/6/2015 11:07:23 AMAPASS
Mark-please call for access Phone #: ###-#### Final ok
ELE15-00017 Electrical Rough-In1/6/20151/6/20151/6/2015 11:06:57 AMPPASS
Mark-please call for access Phone #: ###-#### heat pump rough in ok
ELE14-02213 Electrical Rough-In1/5/20151/6/20151/6/2015 10:25:56 AMAPASS
Mike Phone #: ###-#### Walls and hard lids south of dividing corridor except entry area. Ok to one side x-ray area if contractor wants to allow. Rough in ok cover
ELE14-02747 Rough-In Permanent Service1/5/20151/6/20151/6/2015 9:31:04 AMAPASS
Jason Phone #: ###-#### service for parking lot rough in ok p/s u/g n ok
ELE14-03542 Rough-In Permanent Service1/5/20151/6/20151/6/2015 8:55:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Heath Thomas Rough in ok cover p/s u/g n ok
ELE14-03543 Rough-In Permanent Service1/5/20151/6/20151/6/2015 8:35:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Heath Thomas Rough in ok cover p/s u/g n ok