Inspections for the day of: Tuesday, January 6, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01434 ELE-Aging Inspection1/6/20151/6/20151/6/2015 2:48:07 PM DONE
left correction with person on site, owner is out of town. Phone number listed is currently not working.
ELE14-02598 Final1/5/20151/6/20151/6/2015 2:23:00 PMPFAIL
Paul. After 1:30. Code #11405. Phone #: ###-#### Inspection requested via web by Sean DeLacy
210.8.A.2 GFCI protection required in accessory building with floor at or below grade level, not intended as habitable room, and limited to storage area, work area, or similar use
Spoke to Paul
ELE14-03291 Electrical Rough-In1/5/20151/6/20151/6/2015 1:30:53 PMPFAIL
Tyler// please call before Phone #: ###-####
met owner on site,
need #6 grounding electrode conductor to panels, and down to grounding electrode, verify if supplemental grounding electrode is installed, or add second ground rod.
ELE14-02228 Final1/6/20151/6/20151/6/2015 12:47:37 PMPPASS
Jeff Phone #: ###-####
final OK
ELE14-03406 Final1/6/20151/6/20151/6/2015 12:07:19 PMPCANC
Call Tim if any problems

Ground wire connection has been fixed. Thank you Phone #: ###-#### Inspection requested via web by John Harveywrong inspection, needed perm. service
ELE14-03406 Permanent Service1/6/20151/6/20151/6/2015 12:06:49 PMPPASS
Call Tim if any problems

Ground wire connection has been fixed. Thank you Phone #: ###-#### Inspection requested via web by John Harvey
ground connection fixed, PS, OH, N, OK
ELE15-00028 Final1/6/20151/6/20151/6/2015 11:52:17 AMPPASS
Phone #: ###-#### Inspection requested via web by Shawna Gates//inspection done under ele14-01597
See final on 12-30-14, permit ele14-01597
ELE15-00007 Rough-In Permanent Service1/6/20151/6/20151/6/2015 11:15:43 AMAPASS
call with any questions
thank you Phone #: ###-#### Inspection requested via web by kim grundhauser
RI interior ok to cover, cans in soffit need 2 hour fire barrier before cover. PS, UG, N, OK
ELE14-02853 Final1/5/20151/6/20151/6/2015 10:24:45 AMACANC
Phone #: ###-#### Inspection requested via web by ERIC CENTERS
wrong inspection, needed ri/ps
ELE14-02853 Rough-In Permanent Service1/6/20151/6/20151/6/2015 10:24:44 AMPPASS
Phone #: ###-#### Inspection requested via web by ERIC CENTERS
RI OK to cover, PS, UG, N, OK
ELE14-03546 Rough-In Permanent Service1/5/20151/6/20151/6/2015 9:13:10 AMAPASS
Tom Phone #: ###-####
RI, OK PS, UG, N, OK
ELE14-03553 Rough-In Permanent Service1/6/20151/6/20151/6/2015 9:12:35 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
RI OK, PS, UG, N, OK
ELE14-03250 Final1/5/20151/6/20151/6/2015 8:36:11 AMAPASS
Inspection requested via web by Rowdy Monroe
corrections made final OK