ELE12-01434
| ELE-Aging Inspection | 1/6/2015 | 1/6/2015 | 1/6/2015 2:48:07 PM | | DONE |
|
|
left correction with person on site, owner is out of town. Phone number listed is currently not working.
|
ELE14-02598
| Final | 1/5/2015 | 1/6/2015 | 1/6/2015 2:23:00 PM | P | FAIL |
|
|
Paul. After 1:30. Code #11405. Phone #: ###-#### Inspection requested via web by Sean DeLacy 210.8.A.2 GFCI protection required in accessory building with floor at or below grade level, not intended as habitable room, and limited to storage area, work area, or similar use Spoke to Paul
|
ELE14-03291
| Electrical Rough-In | 1/5/2015 | 1/6/2015 | 1/6/2015 1:30:53 PM | P | FAIL |
|
|
Tyler// please call before Phone #: ###-#### met owner on site, need #6 grounding electrode conductor to panels, and down to grounding electrode, verify if supplemental grounding electrode is installed, or add second ground rod.
|
ELE14-02228
| Final | 1/6/2015 | 1/6/2015 | 1/6/2015 12:47:37 PM | P | PASS |
|
|
Jeff Phone #: ###-#### final OK
|
ELE14-03406
| Final | 1/6/2015 | 1/6/2015 | 1/6/2015 12:07:19 PM | P | CANC |
|
|
Call Tim if any problems
Ground wire connection has been fixed. Thank you Phone #: ###-#### Inspection requested via web by John Harveywrong inspection, needed perm. service
|
ELE14-03406
| Permanent Service | 1/6/2015 | 1/6/2015 | 1/6/2015 12:06:49 PM | P | PASS |
|
|
Call Tim if any problems
Ground wire connection has been fixed. Thank you Phone #: ###-#### Inspection requested via web by John Harvey ground connection fixed, PS, OH, N, OK
|
ELE15-00028
| Final | 1/6/2015 | 1/6/2015 | 1/6/2015 11:52:17 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Shawna Gates//inspection done under ele14-01597 See final on 12-30-14, permit ele14-01597
|
ELE15-00007
| Rough-In Permanent Service | 1/6/2015 | 1/6/2015 | 1/6/2015 11:15:43 AM | A | PASS |
|
|
call with any questions thank you Phone #: ###-#### Inspection requested via web by kim grundhauser RI interior ok to cover, cans in soffit need 2 hour fire barrier before cover. PS, UG, N, OK
|
ELE14-02853
| Final | 1/5/2015 | 1/6/2015 | 1/6/2015 10:24:45 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by ERIC CENTERS wrong inspection, needed ri/ps
|
ELE14-02853
| Rough-In Permanent Service | 1/6/2015 | 1/6/2015 | 1/6/2015 10:24:44 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by ERIC CENTERS RI OK to cover, PS, UG, N, OK
|
ELE14-03546
| Rough-In Permanent Service | 1/5/2015 | 1/6/2015 | 1/6/2015 9:13:10 AM | A | PASS |
|
|
Tom Phone #: ###-#### RI, OK PS, UG, N, OK
|
ELE14-03553
| Rough-In Permanent Service | 1/6/2015 | 1/6/2015 | 1/6/2015 9:12:35 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn RI OK, PS, UG, N, OK
|
ELE14-03250
| Final | 1/5/2015 | 1/6/2015 | 1/6/2015 8:36:11 AM | A | PASS |
|
|
Inspection requested via web by Rowdy Monroe corrections made final OK
|