Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC13-05284 Conference1/6/20151/6/20151/8/2015 11:34:11 AMPPASS
need to contact contractor as no inspections have been requested
MEC14-05180 Final1/5/20151/6/20151/6/2015 11:14:52 AMAFAIL
Phone #: ###-#### Inspection requested via web by Dustin Rich
The return plenum duct to the guru donuts cannot terminate above ceiling and be an open plenum. Need to duct return to kitchen and office area.
The bread oven is not shown on the plans. The engineer needs to address how the heat from the oven is to be removed from the space.