Inspections for the day of: Wednesday, January 6, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00731 ELE-Aging Inspection1/6/20161/6/20161/6/2016 3:22:42 PM DONE
Owner refusing to comply
ELE13-01583 Final1/6/20161/6/20161/6/2016 3:10:27 PMPPASS
Called, contractor happened to be on site so wint and met, walked circuits. Final ok
ELE15-03811 Final1/6/20161/6/20161/6/2016 2:46:22 PMPPASS
Call Jeff when in route. Obtain visitors badge from front desk. Phone #: ###-#### Inspection requested via web by Steve McCloy Final ok
ELE15-03984 Conference1/6/20161/6/20161/6/2016 2:17:28 PMPDONE
2nd meeting for addition of transfer switches and generators.
230.2(A)(4)- grouping not required for optional stand by systems,
110.26- panic hardware and door swings to be corrected.
All service entrance conductors will satisfy 230.6 with interior trans switch installed over underground service entrance and fused outdoor transfer switch.
ELE15-04147 Electrical Rough-In1/5/20161/6/20161/6/2016 11:28:07 AMAPART
If you have any questions, please call Calvin ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 210.52- Wall space in dining room to require receptacle and 2nd basin in master bath to require receptacle.
ok to insulate only
ELE16-00032 Final1/5/20161/6/20161/6/2016 11:20:16 AMAFAIL
This inspections if for a walk in beer cooler. Phone #: ###-#### Inspection requested via web by Warren Fry
Unable to do inspection building permit under review at time of inspection.
ELE15-03984 Conference1/5/20161/6/20161/6/2016 9:47:57 AMADONE
We are requesting a consult. Our contact is Rich @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Discussed the relocating of unfused service entrance conductors for the addition of generator and transfer switches. Talked about NEC 230.6 service entrance shall need to remain or need to be considered outside building until fused which shall be encased in minimum of 2" of concrete or run under 18" of earth or other recognized form.
ELE16-00024 Temporary Service1/4/20161/6/20161/6/2016 8:48:59 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson
t/s u/g n ok