ELE13-00731
| ELE-Aging Inspection | 1/6/2016 | 1/6/2016 | 1/6/2016 3:22:42 PM | | DONE |
|
|
Owner refusing to comply
|
ELE13-01583
| Final | 1/6/2016 | 1/6/2016 | 1/6/2016 3:10:27 PM | P | PASS |
|
|
Called, contractor happened to be on site so wint and met, walked circuits. Final ok
|
ELE15-03811
| Final | 1/6/2016 | 1/6/2016 | 1/6/2016 2:46:22 PM | P | PASS |
|
|
Call Jeff when in route. Obtain visitors badge from front desk. Phone #: ###-#### Inspection requested via web by Steve McCloy Final ok
|
ELE15-03984
| Conference | 1/6/2016 | 1/6/2016 | 1/6/2016 2:17:28 PM | P | DONE |
|
|
2nd meeting for addition of transfer switches and generators. 230.2(A)(4)- grouping not required for optional stand by systems, 110.26- panic hardware and door swings to be corrected. All service entrance conductors will satisfy 230.6 with interior trans switch installed over underground service entrance and fused outdoor transfer switch.
|
ELE15-04147
| Electrical Rough-In | 1/5/2016 | 1/6/2016 | 1/6/2016 11:28:07 AM | A | PART |
|
|
If you have any questions, please call Calvin ###-####. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan 210.52- Wall space in dining room to require receptacle and 2nd basin in master bath to require receptacle. ok to insulate only
|
ELE16-00032
| Final | 1/5/2016 | 1/6/2016 | 1/6/2016 11:20:16 AM | A | FAIL |
|
|
This inspections if for a walk in beer cooler. Phone #: ###-#### Inspection requested via web by Warren Fry Unable to do inspection building permit under review at time of inspection.
|
ELE15-03984
| Conference | 1/5/2016 | 1/6/2016 | 1/6/2016 9:47:57 AM | A | DONE |
|
|
We are requesting a consult. Our contact is Rich @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Discussed the relocating of unfused service entrance conductors for the addition of generator and transfer switches. Talked about NEC 230.6 service entrance shall need to remain or need to be considered outside building until fused which shall be encased in minimum of 2" of concrete or run under 18" of earth or other recognized form.
|
ELE16-00024
| Temporary Service | 1/4/2016 | 1/6/2016 | 1/6/2016 8:48:59 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson t/s u/g n ok
|