GCB15-00063
| FIRE-Conference | 1/6/2016 | 1/6/2016 | 1/6/2016 2:26:41 PM | P | DONE |
|
|
John Chehey and I went over life safety requierments for a temporary occupancy for the "Tasting" area. I deferred him to Scott Arellano for the actual temporary request. I noted that the building address of 2900 chinden is incorrect on the computer as well.
|
FIR15-00898
| INSP-Final Inspection | 1/6/2016 | 1/6/2016 | 1/6/2016 1:18:59 PM | P | PASS |
|
|
Permit finaled
|
NAF15-00041
| INSP-Sprinkler Rough-in | 1/5/2016 | 1/6/2016 | 1/6/2016 11:08:39 AM | A | PART |
|
|
Underground supply line is ok to cover from tap to the sidewalk.
|
NAF15-00040
| INSP-Sprinkler Rough-in | 1/5/2016 | 1/6/2016 | 1/6/2016 11:08:12 AM | A | PART |
|
|
Underground supply line is ok to cover from tap to the sidewalk.
|
NAF15-00039
| INSP-Sprinkler Rough-in | 1/5/2016 | 1/6/2016 | 1/6/2016 11:05:37 AM | A | PART |
|
|
Underground supply line is ok to cover from tap to the sidewalk.
|
NAF15-00038
| INSP-Sprinkler Rough-in/Hydro | 1/5/2016 | 1/6/2016 | 1/6/2016 11:05:09 AM | A | PART |
|
|
Underground supply line is ok to cover from tap to the sidewalk.
|
NAF15-00042
| INSP-Sprinkler Rough-in | 1/5/2016 | 1/6/2016 | 1/6/2016 11:03:38 AM | A | PART |
|
|
Underground supply line is ok to cover from tap to the sidewalk.
|
NAF15-00042
| INSP-Sprinkler Rough-in/Hydro | 1/5/2016 | 1/6/2016 | 1/6/2016 11:02:44 AM | A | PART |
|
|
Underground supply line is ok to cover from tap to the sidewalk.
|
BLD15-00647
| FIRE-Final Inspection | 1/6/2016 | 1/6/2016 | 1/6/2016 10:21:04 AM | P | PASS |
|
|
Life safety passed
|
BLD15-03464
| FIRE-Final Inspection | 1/6/2016 | 1/6/2016 | 1/6/2016 9:52:20 AM | P | PART |
|
|
A temp is being given until the sync module is installed. I had a conversation with State Fire the general contractor and the building maintenance supervisor about what has been installed to match existing does not meet current code for syncing of visual and audio devices and that when another remodel is this area all devices will need to be brought up to current code. All parties agreed and the building supervisor stated that a total alarm upgrade was in the works.
|
FIR15-00908
| INSP-Final Inspection | 1/6/2016 | 1/6/2016 | 1/6/2016 9:50:29 AM | P | PART |
|
|
A temp is being given until the sync module is installed. I had a conversation with State Fire the general contractor and the building maintenance supervisor about what has been installed to match existing does not meet current code for syncing of visual and audio devices and that when another remodel is this area all devices will need to be brought up to current code. All parties agreed and the building supervisor stated that a total alarm upgrade was in the works.
|
NAF15-00041
| INSP-Sprinkler Rough-in | 1/5/2016 | 1/6/2016 | 1/5/2016 1:44:27 PM | A | PART |
|
|
Underground ok to cover up to sidewalk
|
NAF15-00040
| INSP-Sprinkler Rough-in | 1/5/2016 | 1/6/2016 | 1/5/2016 1:43:38 PM | A | PART |
|
|
Underground ok to cover up to sidewalk
|
NAF15-00038
| INSP-Sprinkler Rough-in | 1/5/2016 | 1/6/2016 | 1/5/2016 1:43:07 PM | A | PART |
|
|
Underground ok to cover up to sidewalk
|
NAF15-00039
| INSP-Sprinkler Rough-in | 1/5/2016 | 1/6/2016 | 1/5/2016 1:41:43 PM | A | FAIL |
|
|
Minumum 4'6" bury dept not met.
|