Inspections for the day of: Friday, January 6, 2017.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00062 FIR-Aging Inspection1/6/20171/6/20171/9/2017 7:10:30 AM NR
Contractor is out of business
FIR16-00305 INSP-Sprinkler Rough-in/Hydro1/5/20171/6/20171/6/2017 11:47:15 AMAPASS
Hydro test for the 6th floor passed.
BLD16-03041 FIRE-Final Inspection1/5/20171/6/20171/6/2017 9:01:59 AMAPART
Phase 1 life safety is complete/passed. However prior to a phase 2/final sign off the thumbturn dead bolt in the phase 1 area will need to be removed and the two remote annunciators for the duct smoke detectors will need to be repaired (shows no power) or approval from the mechanical engineer to remove the two duct detector/annunciators. Per the mechanical plans the cfm is well below the 2,000 limit.
BLD16-03662 FIRE-Final Inspection1/5/20171/6/20171/6/2017 7:30:50 AMACANC
randy Phone #: ###-####
FIR16-00310 INSP-Final Inspection12/30/20161/6/20171/6/2017 6:55:47 AMACANC
Troy Nelson is our foreman ###-#### Phone #: ###-#### >> Inspection requested via web by Brad Bettencourt Inspection cancelled from web by: Brad Bettencourt
FIR16-00337 INSP-Final Inspection1/3/20171/6/20171/6/2017 6:35:52 AMACANC
As early as possible Phone #: 2089414511 >> Inspection requested via mobile web by Nathan Price Inspection cancelled via mobile web on Friday, January 06, 2017.
FIR16-00776 INSP-Final Inspection1/5/20171/6/20171/5/2017 2:35:47 PMAPASS
permit finaled