Inspections for the day of: Monday, January 6, 2020.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03663 Final1/6/20201/6/20201/6/2020 3:19:38 PMPPASS
Garage code 1234 Phone #: ###-#### Inspection requested via web by William Andrews Final ok
ELE19-03436 Final1/6/20201/6/20201/6/2020 2:48:32 PMPPASS
Garage code 1234 Phone #: ###-#### Inspection requested via web by William Andrews Final ok
MIS20-00004 ELE-Conference1/6/20201/6/20201/6/2020 2:48:02 PMPCANC
I created a conference, this is a duplicate request.
ELE19-03435 Final1/6/20201/6/20201/6/2020 2:47:21 PMPPASS
Garage code 1234 Phone #: ###-#### Inspection requested via web by William Andrews Final ok
ELE20-00039 Final1/6/20201/6/20201/6/2020 2:07:44 PMPPASS
rocky Phone #: ###-####
Had flexible cords feeding ATM removed from millwork wall as per 400.12(2). Final ok
ELE19-03435 Electrical Rough-In1/6/20201/6/20201/6/2020 2:07:28 PMPPASS
Garage code 1234 Phone #: ###-#### Inspection requested via web by William Andrews Add receptacle for ATM at end of cabinet. Millwork wall rough in ok cover.
MIS20-00004 ELE-Conference1/6/20201/6/20201/6/2020 1:52:09 PMPFAIL
Had a report of violation. An airline has at some point been ran through a panel board on right.
300.8- Installation of conductors with other systems. Raceways and cable trays containing electrical conductors shall not contain any pipe, tube, or equal for steam, water, air, gas, drainage, or any service other than electrical.
Remove air line from reght panel board.
ELE20-00029 Final1/3/20201/6/20201/6/2020 11:56:31 AMAPASS
Contact Andrea Richardson, electrician onsite, 30 before inspection so she can meet you there and show extent of work.
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
ELE20-00029 Electrical Rough-In1/6/20201/6/20201/6/2020 9:43:47 AMPPASS
Contact Andrea Richardson, electrician onsite, 30 before inspection so she can meet you there and show extent of work.
Thank you,
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Called and had Brittani attach ELE to BLD19-02595. All work fished in. Rough in ok.
ELE20-00032 Electrical Rough-In1/3/20201/6/20201/6/2020 9:27:53 AMAPASS
Please call Dan prior to arrival. Thank you! Phone #: ###-#### Inspection requested via web by Lynn Proctor
Called and had Gemma attach ELE to BLD19-04631. Walls for printer room rough in ok cover.