FIR02-00271
| FIR-Aging Inspection | 1/7/2003 | 1/7/2003 | 1/7/2003 12:00:00 AM | | PART |
|
|
called Dan B and left message about the status of this permit 1/7/2003 10:59:25 AM
|
FIR02-00338
| INSP-Sprinkler Rough-in/Hydro | 1/7/2003 | 1/7/2003 | 1/7/2003 12:00:00 AM | A | PART |
|
|
UG hydro okay
|
FIR02-00338
| INSP-Sprinkler Rough-in/Hydro | 1/7/2003 | 1/7/2003 | 1/7/2003 12:00:00 AM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung partial r/i as not all heads are completed; need high temp head at heater in west bay; heads obstructed by cabinets in 2 sleeping rooms on south side; main missing hanger in west bay; need head in electrical room; need drum drip on inspectors test 1/7/2003 11:33:05 AM
|