Inspections for the day of: Tuesday, January 7, 2003.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00271 FIR-Aging Inspection1/7/20031/7/20031/7/2003 12:00:00 AM PART
called Dan B and left message about the status of this permit 1/7/2003 10:59:25 AM
FIR02-00338 INSP-Sprinkler Rough-in/Hydro1/7/20031/7/20031/7/2003 12:00:00 AMAPART
UG hydro okay
FIR02-00338 INSP-Sprinkler Rough-in/Hydro1/7/20031/7/20031/7/2003 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung partial r/i as not all heads are completed; need high temp head at heater in west bay; heads obstructed by cabinets in 2 sleeping rooms on south side; main missing hanger in west bay; need head in electrical room; need drum drip on inspectors test 1/7/2003 11:33:05 AM