Inspections for the day of: Wednesday, January 7, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD03-02693 FIRE-Final Inspection1/2/20041/7/20041/7/2004 12:00:00 AMAPASS
jack ###-#### Fire life safety OK 1/7/2004 9:31:10 AM
FIR03-00480 INSP-Sprinkler Rough-in/Hydro1/6/20041/7/20041/7/2004 12:00:00 AMAPART
rick ; Phone #: ###-#### See approved plans for locations that are ok to cover with todays date 1/7/2004 11:23:25 AM
BLD03-02460 FIRE-Final Inspection1/6/20041/7/20041/7/2004 12:00:00 AMAFAIL
No approved plan/notes on site. There is a separate building permit for this project that has not been approved yet. Per Bill Alexander storage height must remain below 12' until the building has been verifed through the outstanding building permit. The building representative was notified of the storage height issue through a correction notice 1/7/2004 11:25:50 AM
MIS04-00004 FIR-Final1/7/20041/7/20041/7/2004 12:00:00 AMPFAIL
###-#### hal Provide annual inspection for the fire extinguisher and mount at 48" in a normal path of travel, Provide "Door to remain unlocked" sticker, Provide sprinkler protection in the cooler. Repair or remove the exit sign 1/7/2004 3:00:20 PM
BLD03-00321 FIRE-Final Inspection1/7/20041/7/20041/7/2004 12:00:00 AMPPASS
Fire life safety finaled. When tenants move in and pull the separate permits, sprinkler deficiencies in the ware house area will have to be addressed. Specifically upright heads over space at draft curtains. 1/7/2004 5:09:22 PM