Inspections for the day of: Friday, January 7, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy James
TitleMEC-COM/RES INSPECTOR
Phone #794-9461
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC04-03080 Rough-in1/6/20051/7/20051/7/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
verify light to furnace in attic at final 1/7/2005 10:30:44 AM
MEC04-03080 Pressure Test1/6/20051/7/20051/7/2005 12:00:00 AMAPASS
Phone #: ###-#### Internet Inspection Request from: APRIL THOMAS
MEC04-03473 Rough-in1/6/20051/7/20051/7/2005 12:00:00 AMAFAIL
Inspector ran out of time, this is second request.; Phone #: ###-#### Internet Inspection Request from: Matt Hansen
Need pressure test to gas line. Dixie and or I do not remember doing pressure test at shell. 1/7/2005 10:07:05 AM
MEC05-00047 Pressure Test1/6/20051/7/20051/7/2005 12:00:00 AMANR
Scheduled by a contractor via Hello! on 1/6/2005 at 3:02:24 PM. Contact: ###-####. owner decided to add barbeque 1/7/2005 9:15:33 AM
MEC05-00062 Rough-in1/6/20051/7/20051/7/2005 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson
regulator required to be installed horizontal per installation instructions for ventless regulator, nail plates at csst piping, need installation instructions for flue at instant water heater under stairs , need exhaust fan in shower west upper side of house1/7/2005 2:36:53 PM 1/7/2005 2:40:49 PM
MEC05-00062 Pressure Test1/6/20051/7/20051/7/2005 12:00:00 AMPFAIL
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson
MEC04-03306 Final1/7/20051/7/20051/7/2005 12:00:00 AMPFAIL
jr Note: exhaust hood; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
grease exhaust to close to parapet wall, need fire wrap where penetrate roof, grease duct at exhaust fan has no slope to duct, air balance does not meet required design per code. 1/7/2005 4:00:10 PM