Inspections for the day of: Monday, January 7, 2008.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03419 Final1/7/20081/7/20081/7/2008 4:14:57 PMPPASS
Bob, Please call Pat Gill at ###-####, before going to this job. (Raina Wilson, change out service on house). Thank You Phone #: ###-#### Internet Inspection Request from: Debby Ellis called contractor, ok to final
ELE07-04059 Electrical Rough-In1/4/20081/7/20081/7/2008 3:16:03 PMPPASS
john Phone #: ###-#### ric ok, will see closet wall at final in bath area on west side, main level (providing he builds wall)
ELE07-02794 Final1/7/20081/7/20081/7/2008 2:17:12 PMPPASS
mike Phone #: ###-#### ok to final
ELE08-00041 Rough-In Permanent Service1/7/20081/7/20081/7/2008 1:31:49 PMPFAIL
Electrician is Tom Wonacott Phone #: ###-#### Internet Inspection Request from: Jarrod Clyme called, left correction notice, BCC no violations shall be retained, NEC 110.26 shall provide access to electrical equipment, 408.4 circuit directory shall be clear, concise and explanatory for each circuit, 406.8(B) shall use in-use cover for receptacle in wet location,334.12(B) shall not use nm cable exposed or in commercial building, 358.30 emt shall be supported within 3' of box, NOTE: Partial inspection only until access is provided reviewed with owner, told electrician bush removal might be ok for access
ELE07-02673 Final1/7/20081/7/20081/7/2008 12:41:26 PMPPASS
zornic cell ####-#### Phone #: ###-#### ok to final
ELE07-01903 Final1/5/20081/7/20081/7/2008 10:58:02 AMAPASS
Garage Entrance Code is 1400E Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok to final
ELE07-03242 Final1/5/20081/7/20081/7/2008 10:22:43 AMAPASS
Garage Entrance Code is 1968E Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok to final
ELE07-03298 Permanent Service1/4/20081/7/20081/7/2008 9:09:03 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot p/s u/g n ok-1 meter only
ELE07-02040 Final1/4/20081/7/20081/7/2008 8:39:09 AMAPASS
Need final inspection Key will be on the electric meter for door Phone #: ###-#### Internet Inspection Request from: Lynn Cable called contractor, ok to final