FIR07-00147
| INSP-Final Inspection | 1/7/2008 | 1/7/2008 | 1/7/2008 5:03:39 PM | P | DEFR |
|
|
Inspection rescheduled.
|
FIR07-00989
| INSP-Sprinkler Rough-in/Hydro | 1/4/2008 | 1/7/2008 | 1/7/2008 5:02:04 PM | P | PART |
|
|
Overhead hydrostatic test of the new system piping passed, discussed project phase and final inspections.
|
FIR07-00817
| INSP-Sprinkler Rough-in | 1/7/2008 | 1/7/2008 | 1/7/2008 5:00:39 PM | P | PART |
|
|
UG supply line stub out and remote FDC stub to a point 6 feet outside the building stem wall at the east side of the west building are okay for bury.
|
BLD07-01949
| FIRE-Final Inspection | 1/7/2008 | 1/7/2008 | 1/7/2008 4:29:21 PM | P | PASS |
|
|
Fire life safty passed.KR
|
FIR07-00923
| INSP-Final Inspection | 1/7/2008 | 1/7/2008 | 1/7/2008 4:28:30 PM | P | PASS |
|
|
Corrections made per Forest notes for area of seperation.KR
|
FIR07-00951
| INSP-Final Inspection | 1/4/2008 | 1/7/2008 | 1/7/2008 4:21:15 PM | P | PASS |
|
|
corrections made per Troys notes.KR
|
BLD07-02798
| FIRE-Final Inspection | 1/4/2008 | 1/7/2008 | 1/7/2008 3:34:44 PM | P | FAIL |
|
|
Missing approved plan set on site for review, need to provide signage at the main entry/exit door, repair exit signs and EM lighting at two locations.
|
FIR07-01004
| INSP-Final Inspection | 1/7/2008 | 1/7/2008 | 1/7/2008 1:44:51 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR06-00540
| INSP-Sprinkler Rough-in/Hydro | 1/4/2008 | 1/7/2008 | 1/7/2008 1:42:28 PM | A | PART |
|
|
Noted on plans areas approved for cover at the drop ceilings 5th floor south and southeast. Also noted plans do not indicate sprinkler coverage to be provided at the 5th floor elevator lobby.
|
FIR07-00473
| INSP-Alarm Testing | 1/7/2008 | 1/7/2008 | 1/7/2008 12:42:02 PM | A | NR |
|
|
Need NFPA 72 forms completed, jobsite is not in condition for final alarm permit approval due to construction currently underway.
|
BLD06-03529
| FIRE-Final Inspection | 1/4/2008 | 1/7/2008 | 1/7/2008 12:40:14 PM | A | NR |
|
|
Project is not in condition for a final fire life safety approval.
|
BLD06-03525
| FIRE-Final Inspection | 1/4/2008 | 1/7/2008 | 1/7/2008 12:39:00 PM | A | PART |
|
|
Fire life safety is satisfactory, final pending shell permit final.
|
FIR07-00649
| INSP-Final Inspection | 1/7/2008 | 1/7/2008 | 1/7/2008 12:37:10 PM | P | PASS |
|
|
Fire alarm work passed inspection after adjustments made while on site, permit finaled.
|
FIR07-00151
| INSP-Final Inspection | 1/4/2008 | 1/7/2008 | 1/7/2008 12:35:51 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD06-03528
| FIRE-Final Inspection | 1/4/2008 | 1/7/2008 | 1/7/2008 11:20:55 AM | A | FAIL |
|
|
Missing inspections and permit finals for the fire sprinkler and alarm work associated with this building permit number.
|
BLD06-03518
| FIRE-Final Inspection | 1/4/2008 | 1/7/2008 | 1/7/2008 11:17:57 AM | A | FAIL |
|
|
Need project related fire alarm and fire sprinkler permit inspections, approvals and finals prior to life safety final.
|
FIR07-00692
| FIR-Aging Inspection | 1/7/2008 | 1/7/2008 | 1/7/2008 8:13:27 AM | | DEFR |
|
|
wip
|