Inspections for the day of: Monday, January 7, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00147 INSP-Final Inspection1/7/20081/7/20081/7/2008 5:03:39 PMPDEFR
Inspection rescheduled.
FIR07-00989 INSP-Sprinkler Rough-in/Hydro1/4/20081/7/20081/7/2008 5:02:04 PMPPART
Overhead hydrostatic test of the new system piping passed, discussed project phase and final inspections.
FIR07-00817 INSP-Sprinkler Rough-in1/7/20081/7/20081/7/2008 5:00:39 PMPPART
UG supply line stub out and remote FDC stub to a point 6 feet outside the building stem wall at the east side of the west building are okay for bury.
BLD07-01949 FIRE-Final Inspection1/7/20081/7/20081/7/2008 4:29:21 PMPPASS
Fire life safty passed.KR
FIR07-00923 INSP-Final Inspection1/7/20081/7/20081/7/2008 4:28:30 PMPPASS
Corrections made per Forest notes for area of seperation.KR
FIR07-00951 INSP-Final Inspection1/4/20081/7/20081/7/2008 4:21:15 PMPPASS
corrections made per Troys notes.KR
BLD07-02798 FIRE-Final Inspection1/4/20081/7/20081/7/2008 3:34:44 PMPFAIL
Missing approved plan set on site for review, need to provide signage at the main entry/exit door, repair exit signs and EM lighting at two locations.
FIR07-01004 INSP-Final Inspection1/7/20081/7/20081/7/2008 1:44:51 PMPPASS
Fire sprinkler permit finaled.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro1/4/20081/7/20081/7/2008 1:42:28 PMAPART
Noted on plans areas approved for cover at the drop ceilings 5th floor south and southeast. Also noted plans do not indicate sprinkler coverage to be provided at the 5th floor elevator lobby.
FIR07-00473 INSP-Alarm Testing1/7/20081/7/20081/7/2008 12:42:02 PMANR
Need NFPA 72 forms completed, jobsite is not in condition for final alarm permit approval due to construction currently underway.
BLD06-03529 FIRE-Final Inspection1/4/20081/7/20081/7/2008 12:40:14 PMANR
Project is not in condition for a final fire life safety approval.
BLD06-03525 FIRE-Final Inspection1/4/20081/7/20081/7/2008 12:39:00 PMAPART
Fire life safety is satisfactory, final pending shell permit final.
FIR07-00649 INSP-Final Inspection1/7/20081/7/20081/7/2008 12:37:10 PMPPASS
Fire alarm work passed inspection after adjustments made while on site, permit finaled.
FIR07-00151 INSP-Final Inspection1/4/20081/7/20081/7/2008 12:35:51 PMAPASS
Fire sprinkler permit finaled.
BLD06-03528 FIRE-Final Inspection1/4/20081/7/20081/7/2008 11:20:55 AMAFAIL
Missing inspections and permit finals for the fire sprinkler and alarm work associated with this building permit number.
BLD06-03518 FIRE-Final Inspection1/4/20081/7/20081/7/2008 11:17:57 AMAFAIL
Need project related fire alarm and fire sprinkler permit inspections, approvals and finals prior to life safety final.
FIR07-00692 FIR-Aging Inspection1/7/20081/7/20081/7/2008 8:13:27 AM DEFR
wip