ELE08-03244
| Conference | 1/5/2009 | 1/7/2009 | 1/7/2009 2:41:46 PM | P | DONE |
|
|
james Phone #: ###-#### correction posted for work done without permit , shall grd all boxes, provide 15 amp max protection for #14 or replace with #12 note all wiring shall meet 2008 NEC
|
ELE08-02642
| Final | 1/7/2009 | 1/7/2009 | 1/7/2009 1:56:19 PM | P | PASS |
|
|
terry - please call 1/2 hr prior so he can meet you there Phone #: ###-####ok card signed and documentaion of area verified with engineer statement
|
ELE08-03127
| Electrical Rough-In | 1/6/2009 | 1/7/2009 | 1/7/2009 1:03:26 PM | P | FAIL |
|
|
Contact: Mark Zaleski Phone #: ###-#### Internet Inspection Request from: Deb Gooden see added conference
|
ELE08-03127
| Conference | 1/7/2009 | 1/7/2009 | 1/7/2009 1:03:20 PM | P | DONE |
|
|
Contact: Mark Zaleski Phone #: ###-#### Internet Inspection Request from: Deb Gooden met contr needs insulation removed (covered before inspection, 300.4 nail plates, and 11/4", also move sheetrock away from walls so I can inspect also spacing kit. countertop outlets by sink, also loose splices at boxes
|
ESC08-00698
| General Inspection | 1/7/2009 | 1/7/2009 | 1/7/2009 12:59:28 PM | P | PASS |
|
|
ok snow covered
|
ELE08-03127
| Permanent Service | 1/7/2009 | 1/7/2009 | 1/7/2009 12:57:28 PM | P | FAIL |
|
|
Contact: Mark Zaleski Phone #: ###-#### Internet Inspection Request from: Deb Gooden met contr, remove hosebib from below p/s, 200 amp p/s requires #4 copper GEC
|
ELE08-00946
| ELE-Aging Inspection | 1/7/2009 | 1/7/2009 | 1/7/2009 10:22:27 AM | | CANC |
|
|
|
ELE08-00946
| DOC - Permit Expired | 1/7/2009 | 1/7/2009 | 1/7/2009 10:22:21 AM | A | PASS |
|
|
called contr told me expire permit
|
ELE08-01307
| ELE-Aging Inspection | 1/7/2009 | 1/7/2009 | 1/7/2009 10:21:40 AM | | CANC |
|
|
|
ELE08-01307
| DOC - Permit Expired | 1/7/2009 | 1/7/2009 | 1/7/2009 10:21:33 AM | A | PASS |
|
|
called contr told me to expire permit
|
ELE08-01522
| ELE-Aging Inspection | 1/7/2009 | 1/7/2009 | 1/7/2009 10:07:08 AM | | CANC |
|
|
|
ELE08-01522
| Final | 1/7/2009 | 1/7/2009 | 1/7/2009 10:06:58 AM | A | FAIL |
|
|
called needs grd rods and bond steel, also bond bushing on 3/4 sevice raceway, 5 days to correct
|
ELE08-03269
| Final | 1/6/2009 | 1/7/2009 | 1/7/2009 9:56:44 AM | A | FAIL |
|
|
doug Phone #: ###-#### corr. called shall terminate GEC to neutral bus200.2(B)and shall bond all metal fittings myers hubs 250.92 note shall request a p/s inspection ,not a final
|
ELE09-00009
| Electrical Rough-In | 1/6/2009 | 1/7/2009 | 1/7/2009 9:06:11 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 1/6/2009 at 1:50:20 PM. Contact: ###-####. no esc walls ok
|