Inspections for the day of: Wednesday, January 7, 2009.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-03244 Conference1/5/20091/7/20091/7/2009 2:41:46 PMPDONE
james Phone #: ###-#### correction posted for work done without permit , shall grd all boxes, provide 15 amp max protection for #14 or replace with #12 note all wiring shall meet 2008 NEC
ELE08-02642 Final1/7/20091/7/20091/7/2009 1:56:19 PMPPASS
terry - please call 1/2 hr prior so he can meet you there Phone #: ###-####ok card signed and documentaion of area verified with engineer statement
ELE08-03127 Electrical Rough-In1/6/20091/7/20091/7/2009 1:03:26 PMPFAIL
Contact: Mark Zaleski Phone #: ###-#### Internet Inspection Request from: Deb Gooden see added conference
ELE08-03127 Conference1/7/20091/7/20091/7/2009 1:03:20 PMPDONE
Contact: Mark Zaleski Phone #: ###-#### Internet Inspection Request from: Deb Gooden met contr needs insulation removed (covered before inspection, 300.4 nail plates, and 11/4", also move sheetrock away from walls so I can inspect also spacing kit. countertop outlets by sink, also loose splices at boxes
ESC08-00698 General Inspection1/7/20091/7/20091/7/2009 12:59:28 PMPPASS
ok snow covered
ELE08-03127 Permanent Service1/7/20091/7/20091/7/2009 12:57:28 PMPFAIL
Contact: Mark Zaleski Phone #: ###-#### Internet Inspection Request from: Deb Gooden met contr, remove hosebib from below p/s, 200 amp p/s requires #4 copper GEC
ELE08-00946 ELE-Aging Inspection1/7/20091/7/20091/7/2009 10:22:27 AM CANC
ELE08-00946 DOC - Permit Expired1/7/20091/7/20091/7/2009 10:22:21 AMAPASS
called contr told me expire permit
ELE08-01307 ELE-Aging Inspection1/7/20091/7/20091/7/2009 10:21:40 AM CANC
ELE08-01307 DOC - Permit Expired1/7/20091/7/20091/7/2009 10:21:33 AMAPASS
called contr told me to expire permit
ELE08-01522 ELE-Aging Inspection1/7/20091/7/20091/7/2009 10:07:08 AM CANC
ELE08-01522 Final1/7/20091/7/20091/7/2009 10:06:58 AMAFAIL
called needs grd rods and bond steel, also bond bushing on 3/4 sevice raceway, 5 days to correct
ELE08-03269 Final1/6/20091/7/20091/7/2009 9:56:44 AMAFAIL
doug Phone #: ###-#### corr. called shall terminate GEC to neutral bus200.2(B)and shall bond all metal fittings myers hubs 250.92 note shall request a p/s inspection ,not a final
ELE09-00009 Electrical Rough-In1/6/20091/7/20091/7/2009 9:06:11 AMAPASS
Scheduled by a contractor via Hello! on 1/6/2009 at 1:50:20 PM. Contact: ###-####. no esc walls ok