Inspections for the day of: Wednesday, January 7, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00632 INSP-Final Inspection1/7/20091/7/20091/8/2009 3:49:48 PMPFAIL
No inspection was performed due to time constraints and the new facp is not utilizing the phone lines as per the approved drawings. It is using a wireless transmitter that has been installed by Alarmco. Alarmco will need to submitt a separate permit for approval to use this device.
FIR07-01032 INSP-Sprinkler Rough-in1/6/20091/7/20091/7/2009 3:28:00 PMPPASS
See the second floor as-built plans for the corridor and dining areas that are approved for cover.
FIR08-00805 INSP-Conference1/5/20091/7/20091/7/2009 3:13:59 PMPDONE
james Phone #: ###-####
FIR08-00861 INSP-Final Inspection1/7/20091/7/20091/7/2009 3:13:17 PMPPASS
permit finaled
BLD08-02267 FIRE-Final Inspection1/7/20091/7/20091/7/2009 12:06:25 PMPPASS
Life safety passed
FIR08-00595 INSP-Conference1/7/20091/7/20091/7/2009 11:38:18 AMPDONE
I spoke to Brian Johnson and to Andy, the builder, about the PIV that was shown to be installed on the overhead sprinkler plans has not been installed. Per the separate underground permit FIR08-00514 no PIV was being installed. The PIV needs to be installed, a wall PIV approved by the city of boise installed or the one hour room with exterior access provided. Brian stated that he would contact me with a solution.
FIR08-00833 INSP-Final Inspection1/7/20091/7/20091/7/2009 11:35:32 AMPPASS
Permit finaled
BLD08-02520 FIRE-Final Inspection1/6/20091/7/20091/7/2009 11:35:02 AMAPASS
Life safety passed
BLD08-00103 FIRE-Final Inspection1/6/20091/7/20091/7/2009 10:26:59 AMAFAIL
Need the project related fire alarm permit finaled. Also need the exit discharge lights installed at both main exits and the exit sign, corridor emergency light and exit discharge light repaired at/in the north exit corridor at the meat department. The west exterior exit door out of the flower service area needs the large metal bar/deadbolt/padlock removed.
FIR08-00520 INSP-Final Inspection1/6/20091/7/20091/7/2009 9:13:28 AMACANC
The hood suppression system has not been tied into the fire alarm system so no inspection was performed.