Inspections for the day of: Tuesday, January 7, 2014.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-03344 Electrical Rough-In1/7/20141/7/20141/7/2014 3:25:49 PMPPASS
Rough in inspection for ceiling of multi purpose room behind sanctuary. Phone #: ###-#### >> Inspection requested via web by Barbara Szurgot rough-in ok cover
ELE13-03111 Final1/7/20141/7/20141/7/2014 3:01:02 PMPPASS
Phone #: ###-#### >> Inspection requested via web by daniel bibikov final ok
ELE14-00037 Conference1/7/20141/7/20141/7/2014 2:31:45 PMPDONE
Please call Jake when you are on your way. Thank You. Phone #: ###-#### >> Inspection requested via web by Clay Morgan Discussed with electrical contractor requirements for rewiring burn structure with residential and commerial use.
ELE14-00031 Conference1/6/20141/7/20141/7/2014 1:49:10 PMPDONE
Ivan Phone #: ###-#### Discussed with homeowner electrical requirements for detached garage
ELE14-00038 Permanent Service1/7/20141/7/20141/7/2014 12:38:29 PMPFAIL
Call for access code - Jay Phone #: ###-#### NEC 110.26 Working space for service panel(Remove shelving) NEC 250.56 Upgrade service grounding to 2008 codes. Replace broken refrigerator receptacle, Provide protection for water heater romex, Install connectors and KO plugs as needed for service panel
ELE12-01444 ELE-Aging Inspection1/7/20141/7/20141/7/2014 10:05:47 AM DONE
Left message with contractor's recoder and posted correction notice on residents door
ELE12-01442 ELE-Aging Inspection1/7/20141/7/20141/7/2014 9:35:13 AM FAIL
NEC 408.4 shall complete meter main and remote panel directory, strap service entrance raiser
ELE10-02481 Final1/7/20141/7/20141/7/2014 9:18:51 AMPPASS
Neutrals and grounding conductor are separated in remote panel, final ok
ELE14-00030 Permanent Service1/6/20141/7/20141/7/2014 8:49:25 AMAPASS
Power off over a year, need inspection of service to get power turned on. Any questions please call Andy @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose p/s o/h rec ok
ELE13-02949 Electrical Rough-In1/6/20141/7/20141/7/2014 8:27:23 AMAPASS
Need inspection to cover conduit inside mechanical room stubbed to warehouse. Phone #: ###-#### >> Inspection requested via web by Alan Lusk rough-in ok
ELE13-02343 Final1/6/20141/7/20141/7/2014 8:07:55 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Corey Welch job complete, final ok