FIR14-00182
| INSP-Alarm Testing | 1/5/2015 | 1/7/2015 | 1/8/2015 4:07:42 PM | P | FAIL |
|
|
Plan modification will be necessary due to numerous changes to the original design and approved plans including; approx 25 new ID detectors, mag locks at three sets of doors, added smoke and heat detection at the elevator hoistway, relocated sprinkler risers, new ADA rooms and notification appliances, revised matrix, etc. Need to provide notification at the gym restroom, post signage at the FACP room door. Elevator is not in service to complete recall and shunt tests.
|
BLD14-03496
| FIRE-Final Inspection | 1/7/2015 | 1/7/2015 | 1/7/2015 3:44:56 PM | P | FAIL |
|
|
C/N items include; repair two existing exit signs, provide two new exit signs at locations discussed, provide plans reflecting revised room usage at rm 344. Missing doors and hardware at some locations.
|
FIR14-00911
| INSP-Final Inspection | 1/7/2015 | 1/7/2015 | 1/7/2015 3:42:43 PM | P | PASS |
|
|
Scope of work completed and passed functional testing. Per general contractor room 344 is no longer a "mothers room" and is now a "storage room"- ref. revised building plans for changes. Fire alarm permit finaled.
|
BLD14-01868
| FIRE-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 2:40:14 PM | A | FAIL |
|
|
Items noted include; trouble condition at the FACP remote annunciator, missing fire sprinkler coverage at the new beer cooler, overspaced sprinkler coverage adjacent to the new cooler, remove keyed lock deadbolt at the basement kitchen exit door, adjust sprinkler coverage at the basement office due to drop ceiling removal.
|
FIR14-00846
| INSP-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 2:27:16 PM | P | PASS |
|
|
Fire sprinkler work passed both rough-in and final inspections. Permit finaled.
|
MIS15-00004
| FIR-Final | 1/6/2015 | 1/7/2015 | 1/7/2015 1:25:12 PM | A | NH |
|
|
No access to complete inspection.
|
FIR14-00672
| INSP-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 1:13:14 PM | A | PASS |
|
|
Scope of permit work completed. Fire sprinkler permit finaled.
|
FIR14-00671
| INSP-Sprinkler Rough-in/Hydro | 1/6/2015 | 1/7/2015 | 1/7/2015 1:11:54 PM | P | PART |
|
|
Concluded satisfactory pneumatic test of the new dry system.
|