Inspections for the day of: Wednesday, January 7, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-03413 FIRE-Conference1/7/20151/7/20151/7/2015 3:18:20 PMPDONE
Went over life safety requirements with the builder. It appears exit signs and emergency ligthing is not required.
NAF14-00028 INSP-Sprinkler Rough-in1/7/20151/7/20151/7/2015 2:49:22 PMPFAIL
Piping that had been previously buried has been removed. No new piping has been installed yet due to contractor (not applicant) waiting for a "road box" to continue installation. Tribal Fire was going to stop at project site and verify installation.
BLD14-00207 FIRE-Final Inspection1/7/20151/7/20151/7/2015 2:24:49 PMPCANC
Canceling due to project related fire alarm and fire sprinkler permits not ready for final inspections. Tyler Phone #: ###-####
FIR14-00653 INSP-Final Inspection1/6/20151/7/20151/7/2015 2:24:03 PMPCANC
Canceling due to fire sprinkler contractor not finishing work for interconnection
FIR14-00420 INSP-Final Inspection1/6/20151/7/20151/7/2015 2:23:19 PMPCANC
Cancel per Brandon Phone #: ###-####
FIR14-00421 INSP-Final Inspection1/6/20151/7/20151/7/2015 2:22:58 PMPCANC
Cancel per Brandon Phone #: ###-####
FIR14-00423 INSP-Final Inspection1/6/20151/7/20151/7/2015 2:22:29 PMPCANC
Cancel per Brandon Phone #: ###-####
NAF14-00021 INSP-Final1/6/20151/7/20151/7/2015 2:22:03 PMPPASS
Permit finaled. Matt is going to provide the required as-builts to Lee.
BLD14-01766 FIRE-Final Inspection1/6/20151/7/20151/7/2015 2:21:12 PMAFAIL
Need project related fire alarm and fire sprinkler permits finaled. Smoke alarm in 201 was repaired and tested ok.
FIR14-00926 INSP-Final Inspection1/6/20151/7/20151/7/2015 2:20:17 PMAFAIL
Flow switch activation registers as com trouble. Two tamper switches are not functional. Testing was stopped.
FIR14-00556 INSP-Final Inspection1/6/20151/7/20151/7/2015 2:19:17 PMAFAIL
Fire alarm interconnection is not functional
BLD14-03665 FIRE-Final Inspection1/6/20151/7/20151/7/2015 9:32:35 AMAFAIL
Repair all exit signs and emergency lighting, provide fire extinguisher for the mezzanine.
BLD14-03162 FIRE-Final Inspection1/6/20151/7/20151/7/2015 9:31:45 AMAPASS
Life safety passed. Owner to provide Occupant Load Sign as designated on the approved plans.