BLD14-03413
| FIRE-Conference | 1/7/2015 | 1/7/2015 | 1/7/2015 3:18:20 PM | P | DONE |
|
|
Went over life safety requirements with the builder. It appears exit signs and emergency ligthing is not required.
|
NAF14-00028
| INSP-Sprinkler Rough-in | 1/7/2015 | 1/7/2015 | 1/7/2015 2:49:22 PM | P | FAIL |
|
|
Piping that had been previously buried has been removed. No new piping has been installed yet due to contractor (not applicant) waiting for a "road box" to continue installation. Tribal Fire was going to stop at project site and verify installation.
|
BLD14-00207
| FIRE-Final Inspection | 1/7/2015 | 1/7/2015 | 1/7/2015 2:24:49 PM | P | CANC |
|
|
Canceling due to project related fire alarm and fire sprinkler permits not ready for final inspections. Tyler Phone #: ###-####
|
FIR14-00653
| INSP-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 2:24:03 PM | P | CANC |
|
|
Canceling due to fire sprinkler contractor not finishing work for interconnection
|
FIR14-00420
| INSP-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 2:23:19 PM | P | CANC |
|
|
Cancel per Brandon Phone #: ###-####
|
FIR14-00421
| INSP-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 2:22:58 PM | P | CANC |
|
|
Cancel per Brandon Phone #: ###-####
|
FIR14-00423
| INSP-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 2:22:29 PM | P | CANC |
|
|
Cancel per Brandon Phone #: ###-####
|
NAF14-00021
| INSP-Final | 1/6/2015 | 1/7/2015 | 1/7/2015 2:22:03 PM | P | PASS |
|
|
Permit finaled. Matt is going to provide the required as-builts to Lee.
|
BLD14-01766
| FIRE-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 2:21:12 PM | A | FAIL |
|
|
Need project related fire alarm and fire sprinkler permits finaled. Smoke alarm in 201 was repaired and tested ok.
|
FIR14-00926
| INSP-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 2:20:17 PM | A | FAIL |
|
|
Flow switch activation registers as com trouble. Two tamper switches are not functional. Testing was stopped.
|
FIR14-00556
| INSP-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 2:19:17 PM | A | FAIL |
|
|
Fire alarm interconnection is not functional
|
BLD14-03665
| FIRE-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 9:32:35 AM | A | FAIL |
|
|
Repair all exit signs and emergency lighting, provide fire extinguisher for the mezzanine.
|
BLD14-03162
| FIRE-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 9:31:45 AM | A | PASS |
|
|
Life safety passed. Owner to provide Occupant Load Sign as designated on the approved plans.
|