Inspections for the day of: Thursday, January 7, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00046 Temporary Service1/7/20161/7/20161/7/2016 2:22:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE13-01646 ELE-Aging Inspection1/7/20161/7/20161/7/2016 1:44:29 PM DONE
Drove by and inspected
ELE13-01646 Final1/7/20161/7/20161/7/2016 1:31:02 PMPPASS
Listing confirmed. Final ok
ELE13-01576 ELE-Aging Inspection1/7/20161/7/20161/7/2016 1:22:15 PM DONE
Drove by and inspected
ELE13-01576 Final1/7/20161/7/20161/7/2016 1:08:52 PMPPASS
UL listing confirmed. Final ok
ELE16-00019 Rough-In Permanent Service1/5/20161/7/20161/7/2016 12:58:26 PMPPASS
Phone #: ###-#### Inspection requested via web by cris flores
Service change only at this time.
p/s u/g rec ok
ELE16-00035 Electrical Rough-In1/7/20161/7/20161/7/2016 12:18:46 PMAPASS
New shop Phone #: ###-#### Inspection requested via web by Greg Idsinga
South truck entrance shop rough ok cover
ELE16-00026 Conference1/6/20161/7/20161/7/2016 11:52:49 AMADONE
Bill Phone #: ###-####
Discussed service change. Will maintain 2' of more from gas meter. Installing meter panel combo. Old panel location in bathroom to change to junction point. All grounding type receptacle outlets to be GFCI protected or changed to ungrounded receptacles. Adding receptacles in bathroom and kitchen for refrigerator and counter to left of refer. Also changing light fixtures
ELE13-01262 ELE-Aging Inspection1/7/20161/7/20161/7/2016 11:16:26 AM DONE
Waiting on owner
ELE15-04135 Final1/6/20161/7/20161/7/2016 11:09:20 AMAPASS
Re-used existing wires from Panel "M" circuit #13 and fed a new 100 amp non-fused disconnect, from this disconnect we fed a new 480v to 240v 3 phase transformer, from the load side of the transformer we fed a new 3 phase 240v 200 amp fused disconnect, from this disconnect we fed the new Cyber Saw, we extended the existing conveyor motor lead from the Cyber Saw to the scrap conveyor. We also used existing conduit from Panel "A" to run a new dedicated 120v 20 amp circuit (#30) to the new computer cabinet for the Cyber Saw. Ask for James. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell Final ok
ELE15-04135 Electrical Rough-In1/6/20161/7/20161/7/2016 11:02:59 AMAPASS
Re-used existing wires from Panel "M" circuit #13 and fed a new 100 amp non-fused disconnect, from this disconnect we fed a new 480v to 240v 3 phase transformer, from the load side of the transformer we fed a new 3 phase 240v 200 amp fused disconnect, from this disconnect we fed the new Cyber Saw, we extended the existing conveyor motor lead from the Cyber Saw to the scrap conveyor. We also used existing conduit from Panel "A" to run a new dedicated 120v 20 amp circuit (#30) to the new computer cabinet for the Cyber Saw. Ask for James. If you have any questions please call Jeremiah at ###-####. Thank you! Phone #: ###-#### Inspection requested via web by Dan Mitchell Rough in ok
ELE15-03932 Electrical Rough-In1/6/20161/7/20161/7/2016 10:25:07 AMAFAIL
Mitch// please call 30min prior Phone #: ###-#### Update receptacles, lighting, and switches, out lighting yet to be installed. Check on final open ground in front north office by door and reverse polarity in front GFI. Out receptacle for AC not working.
110.12(A)- Unused openings shall be sealed.
210.8(B)(8)- All 120 volt receptacle outlets in shop area shall have GFCI protection.
ELE16-00018 Rough-In Permanent Service1/6/20161/7/20161/7/2016 9:11:48 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson
Rough in ok cover p/s u/g n ok
ELE16-00040 Permanent Service1/6/20161/7/20161/7/2016 8:29:44 AMAPASS
We are requesting a permanent service inspection for the warehouse for tomorrow 1/7/15 in the am. Our contact is Rod @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate p/s o/h n ok