ELE19-00062
| Temporary Service | 1/7/2019 | 1/7/2019 | 1/7/2019 3:04:44 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE19-00063
| Temporary Service | 1/7/2019 | 1/7/2019 | 1/7/2019 3:00:59 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn t/s u/g n ok
|
ELE18-04262
| Electrical Rough-In | 1/7/2019 | 1/7/2019 | 1/7/2019 2:47:21 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton New offiices boarders on grid only ok
|
ELE18-03539
| Final | 1/7/2019 | 1/7/2019 | 1/7/2019 2:31:03 PM | P | FAIL |
|
|
garage code 1424 Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Reverse polarity on receptacle on level 2 stair wall. 356.30- FNMC Shall be secured with in 12" of an enclosure then every 6' minimum. Strap AC whip.
|
ELE18-01647
| Electrical Rough-In | 1/4/2019 | 1/7/2019 | 1/7/2019 1:58:37 PM | A | PART |
|
|
Danny. Phone #: ###-#### Inspection requested via web by Sean DeLacy Area C-102, 103, 104, 105, 106, 107, 108, 109, 110, 111, 112, 137, 138, 139, storage 1&2, game room TCO ok. TV / chapel wrong dimmer, light flickered when dimmed, 101- 2 dead receptacles in living area.
|
ELE18-04831
| Rough-In Permanent Service | 1/4/2019 | 1/7/2019 | 1/7/2019 9:33:43 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Ronge receptacle will not be usable due to gas line installed in front of box. 300.15- 14-2 hanging in pantry shall terminate in a box. 590.6(B)- Temp power receptacles other than 120 volt shall have GFCI protecton. All can locations to be a cut in LED recessed luminaire. Called contact, no answer, left message.
|
ELE19-00020
| Electrical Rough-In | 1/7/2019 | 1/7/2019 | 1/7/2019 8:58:20 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mark M Level 4 west sleeping rooms grid rough in ok cover
|