FIR19-00953
| INSP-Sprinkler Rough-in | 1/7/2020 | 1/7/2020 | 1/7/2020 2:47:28 PM | P | PASS |
|
|
Underground supply line issues have been addressed. Piping can be covered.
Kem Phone #: ###-####
|
FIR19-00688
| INSP-Sprinkler Rough-in | 1/2/2020 | 1/7/2020 | 1/7/2020 1:28:42 PM | P | FAIL |
|
|
Provide additional pendant at the main exit and in the combustible concealed space as discussed, insulation at the roof deck needs repaired.
Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR19-00599
| INSP-Sprinkler Rough-in | 1/6/2020 | 1/7/2020 | 1/7/2020 1:27:43 PM | A | PASS |
|
|
All piping is now ok for cover except the Kitchen area which is not complete.
Kenny Caldwell is the contact for this RTC inspection. We appreciate you help. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD19-04843
| FIRE-Final Inspection | 1/6/2020 | 1/7/2020 | 1/7/2020 10:34:28 AM | A | FAIL |
|
|
Provide single action hardware on the rear exit door and remove deadbolts, repair exit signs and emergency lights, hang/tag fire extinguisher in back room, provide sprinkler permit for the sprinkler modifications.
not open until 10 // Jeremy Phone #: ###-####
|
FIR19-00953
| INSP-Sprinkler Rough-in | 1/6/2020 | 1/7/2020 | 1/7/2020 9:19:21 AM | A | FAIL |
|
|
It does not appear the bury depth meets 4'-6" for both the supply and breeze way piping as required by state and local code, the supply piping is utilizing mechanical restraints and the bolts are loose at the point of connection, the mechanical restraints have not been coated as per NFPA 13 10.6.2.5. No piping to be covered. ,
underground - Cam Phone #: ###-####
|
FIR19-00799
| INSP-Sprinkler Rough-in | 1/6/2020 | 1/7/2020 | 1/7/2020 9:05:17 AM | A | CANC |
|
|
To be canceled per James and rescheduled for tomorrow.
Tenting inspection, call before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|