FIR03-00584
| FIR-Aging Inspection | 1/8/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | | NR |
|
|
will need submittals and lights to shut off with extinguishing system 1/8/2004 11:23:51 AM
|
BLD02-02126
| FIRE-Final Inspection | 1/5/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | A | FAIL |
|
|
mike-- ###-#### need to complete alarm and sprinkler permits; need to complete stairwells for egress to include doors and lights 1/8/2004 11:16:01 AM
|
BLD03-01086
| FIRE-Final Inspection | 1/6/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 1/6/2004 at 3:47:08 PM. Contact: ###-####. fire sprinkleres overspaced at new wall; will need submittals 1/8/2004 3:41:51 PM
|
FIR03-00093
| INSP-Final Inspection | 1/8/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | A | FAIL |
|
|
need heaqds replaced that are painted in basement and tape remove from others; hydro FDC; need signage on drains and blue tag on risers; SR head in elevator room; will need test papers at final;resubmittals for basement and fourth floor 1/8/2004 11:11:09 AM
|
FIR03-00075
| INSP-Final Inspection | 1/8/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | A | FAIL |
|
|
standby power draw is higher than calcs (340) so larger amp batteries are needed; resubmittals needed for changes to one line; mount detector at top of stair; need record of completion 1/8/2004 11:14:56 AM
|
FIR03-00093
| INSP-Sprinkler Rough-in/Hydro | 1/8/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | P | FAIL |
|
|
FDC hydro failed to hold pressure 1/8/2004 3:41:06 PM
|
BLD03-01888
| FIRE-Final Inspection | 1/8/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | P | PASS |
|
|
|
MIS03-00247
| FIR-Final | 1/7/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | P | PASS |
|
|
###-#### Spencer
|
FIR03-00437
| INSP-Alarm Testing | 1/8/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | P | PASS |
|
|
cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
|
FIR03-00605
| INSP-Alarm Testing | 1/8/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | P | PASS |
|
|
cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
|
FIR03-00438
| INSP-Final Inspection | 1/8/2004 | 1/8/2004 | 1/8/2004 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 1/8/2004 at 7:04:41 AM. Contact: ###-####.
|