Inspections for the day of: Thursday, January 8, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00584 FIR-Aging Inspection1/8/20041/8/20041/8/2004 12:00:00 AM NR
will need submittals and lights to shut off with extinguishing system 1/8/2004 11:23:51 AM
BLD02-02126 FIRE-Final Inspection1/5/20041/8/20041/8/2004 12:00:00 AMAFAIL
mike-- ###-#### need to complete alarm and sprinkler permits; need to complete stairwells for egress to include doors and lights 1/8/2004 11:16:01 AM
BLD03-01086 FIRE-Final Inspection1/6/20041/8/20041/8/2004 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 1/6/2004 at 3:47:08 PM. Contact: ###-####. fire sprinkleres overspaced at new wall; will need submittals 1/8/2004 3:41:51 PM
FIR03-00093 INSP-Final Inspection1/8/20041/8/20041/8/2004 12:00:00 AMAFAIL
need heaqds replaced that are painted in basement and tape remove from others; hydro FDC; need signage on drains and blue tag on risers; SR head in elevator room; will need test papers at final;resubmittals for basement and fourth floor 1/8/2004 11:11:09 AM
FIR03-00075 INSP-Final Inspection1/8/20041/8/20041/8/2004 12:00:00 AMAFAIL
standby power draw is higher than calcs (340) so larger amp batteries are needed; resubmittals needed for changes to one line; mount detector at top of stair; need record of completion 1/8/2004 11:14:56 AM
FIR03-00093 INSP-Sprinkler Rough-in/Hydro1/8/20041/8/20041/8/2004 12:00:00 AMPFAIL
FDC hydro failed to hold pressure 1/8/2004 3:41:06 PM
BLD03-01888 FIRE-Final Inspection1/8/20041/8/20041/8/2004 12:00:00 AMPPASS
MIS03-00247 FIR-Final1/7/20041/8/20041/8/2004 12:00:00 AMPPASS
###-#### Spencer
FIR03-00437 INSP-Alarm Testing1/8/20041/8/20041/8/2004 12:00:00 AMPPASS
cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR03-00605 INSP-Alarm Testing1/8/20041/8/20041/8/2004 12:00:00 AMPPASS
cell ph. ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Buccino
FIR03-00438 INSP-Final Inspection1/8/20041/8/20041/8/2004 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 1/8/2004 at 7:04:41 AM. Contact: ###-####.