FIR06-00330
| FIR-Aging Inspection | 1/8/2007 | 1/8/2007 | 1/9/2007 1:12:12 PM | | DONE |
|
|
In progress
|
FIR06-00680
| INSP-Final Inspection | 1/8/2007 | 1/8/2007 | 1/8/2007 3:58:54 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR05-00831
| INSP-Final Inspection | 1/8/2007 | 1/8/2007 | 1/8/2007 3:55:59 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR05-00710
| INSP-Sprinkler Rough-in/Hydro | 1/8/2007 | 1/8/2007 | 1/8/2007 3:55:10 PM | P | PART |
|
|
Overhead hydro test passed, noted items missing for final including main drain, riser signage, head box, reliable heat for the riser room, etc.
|
FIR06-01012
| INSP-Final Inspection | 1/5/2007 | 1/8/2007 | 1/8/2007 3:53:46 PM | P | FAIL |
|
|
Phone line 2 trouble does not report, flow switch timing adjusted while on site, NFPA 72 record of inspection and testing should be completed prior to final field inspection.
|
FIR06-01013
| INSP-Final Inspection | 1/5/2007 | 1/8/2007 | 1/8/2007 3:51:46 PM | P | FAIL |
|
|
Alarm work is not ready for final at this time due to program issues.
|
FIR05-00707
| INSP-Sprinkler Rough-in/Hydro | 1/8/2007 | 1/8/2007 | 1/8/2007 3:50:52 PM | P | PART |
|
|
AG hydro passed, noted items missing for final including lack of a sufficient reliable heat source for the riser room, signage, head box, etc.
|
FIR06-01014
| INSP-Final Inspection | 1/5/2007 | 1/8/2007 | 1/8/2007 3:48:56 PM | P | FAIL |
|
|
Need to program phone line 2, pretesting has not been completed.
|
FIR05-00708
| INSP-Sprinkler Rough-in/Hydro | 1/8/2007 | 1/8/2007 | 1/8/2007 3:47:46 PM | P | PART |
|
|
OH hydro passed, noted missing bell sign, head box, signage at the riser room door, the main drain must be piped outside.
|
FIR06-01015
| INSP-Final Inspection | 1/5/2007 | 1/8/2007 | 1/8/2007 3:46:15 PM | P | FAIL |
|
|
Phone line 2 is not programed, outside bell does not function, flow switch timing adjusted while on site, permit work is not ready for final.
|
FIR06-00875
| INSP-Sprinkler Rough-in | 1/8/2007 | 1/8/2007 | 1/8/2007 1:57:32 PM | P | PART |
|
|
OH sprinkler work is good for cover at the drop ceiling areas.
|
FIR05-00710
| INSP-Final Inspection | 1/8/2007 | 1/8/2007 | 1/8/2007 12:24:17 PM | P | CANC |
|
|
Duplicate inspection request.
|
FIR05-00709
| INSP-Final Inspection | 1/8/2007 | 1/8/2007 | 1/8/2007 12:22:47 PM | P | NR |
|
|
derrick - fire life safety ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Hydro test failed, some items not complete for final.
|
FIR05-00709
| INSP-Sprinkler Rough-in/Hydro | 1/8/2007 | 1/8/2007 | 1/8/2007 12:20:44 PM | P | FAIL |
|
|
AG hydro failed due to visible leakage at the riser manifold.
|
BLD05-00807
| FIRE-Final Inspection | 1/5/2007 | 1/8/2007 | 1/8/2007 12:19:24 PM | A | NR |
|
|
The project related fire alarm and sprinkler permits must be inspected and approved prior to life safety final.
|
FIR06-00295
| INSP-Final Inspection | 1/5/2007 | 1/8/2007 | 1/8/2007 10:47:12 AM | A | PASS |
|
|
Fire alarm work passed inspection, zone map updated while on site, contractor to fax 72 forms as discussed.
|