Inspections for the day of: Monday, January 8, 2007.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00330 FIR-Aging Inspection1/8/20071/8/20071/9/2007 1:12:12 PM DONE
In progress
FIR06-00680 INSP-Final Inspection1/8/20071/8/20071/8/2007 3:58:54 PMPPASS
Fire alarm permit finaled.
FIR05-00831 INSP-Final Inspection1/8/20071/8/20071/8/2007 3:55:59 PMPPASS
Fire alarm permit finaled.
FIR05-00710 INSP-Sprinkler Rough-in/Hydro1/8/20071/8/20071/8/2007 3:55:10 PMPPART
Overhead hydro test passed, noted items missing for final including main drain, riser signage, head box, reliable heat for the riser room, etc.
FIR06-01012 INSP-Final Inspection1/5/20071/8/20071/8/2007 3:53:46 PMPFAIL
Phone line 2 trouble does not report, flow switch timing adjusted while on site, NFPA 72 record of inspection and testing should be completed prior to final field inspection.
FIR06-01013 INSP-Final Inspection1/5/20071/8/20071/8/2007 3:51:46 PMPFAIL
Alarm work is not ready for final at this time due to program issues.
FIR05-00707 INSP-Sprinkler Rough-in/Hydro1/8/20071/8/20071/8/2007 3:50:52 PMPPART
AG hydro passed, noted items missing for final including lack of a sufficient reliable heat source for the riser room, signage, head box, etc.
FIR06-01014 INSP-Final Inspection1/5/20071/8/20071/8/2007 3:48:56 PMPFAIL
Need to program phone line 2, pretesting has not been completed.
FIR05-00708 INSP-Sprinkler Rough-in/Hydro1/8/20071/8/20071/8/2007 3:47:46 PMPPART
OH hydro passed, noted missing bell sign, head box, signage at the riser room door, the main drain must be piped outside.
FIR06-01015 INSP-Final Inspection1/5/20071/8/20071/8/2007 3:46:15 PMPFAIL
Phone line 2 is not programed, outside bell does not function, flow switch timing adjusted while on site, permit work is not ready for final.
FIR06-00875 INSP-Sprinkler Rough-in1/8/20071/8/20071/8/2007 1:57:32 PMPPART
OH sprinkler work is good for cover at the drop ceiling areas.
FIR05-00710 INSP-Final Inspection1/8/20071/8/20071/8/2007 12:24:17 PMPCANC
Duplicate inspection request.
FIR05-00709 INSP-Final Inspection1/8/20071/8/20071/8/2007 12:22:47 PMPNR
derrick - fire life safety ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Hydro test failed, some items not complete for final.
FIR05-00709 INSP-Sprinkler Rough-in/Hydro1/8/20071/8/20071/8/2007 12:20:44 PMPFAIL
AG hydro failed due to visible leakage at the riser manifold.
BLD05-00807 FIRE-Final Inspection1/5/20071/8/20071/8/2007 12:19:24 PMANR
The project related fire alarm and sprinkler permits must be inspected and approved prior to life safety final.
FIR06-00295 INSP-Final Inspection1/5/20071/8/20071/8/2007 10:47:12 AMAPASS
Fire alarm work passed inspection, zone map updated while on site, contractor to fax 72 forms as discussed.