FIR07-00707
| INSP-Final Inspection | 1/7/2008 | 1/8/2008 | 1/8/2008 4:28:52 PM | P | FAIL |
|
|
The riser needs to be located within 1 1/2" of the wall as per the installation guide. Alarm interconnection needs to be tested. Underground flush is passed.
|
FIR07-00886
| INSP-Supply line flush | 1/8/2008 | 1/8/2008 | 1/8/2008 4:26:50 PM | P | PASS |
|
|
Underground flush passed.
|
FIR07-00887
| INSP-Supply line flush | 1/8/2008 | 1/8/2008 | 1/8/2008 2:41:21 PM | P | PASS |
|
|
Underground flush passed.
|
FIR07-00779
| INSP-Final Inspection | 1/8/2008 | 1/8/2008 | 1/8/2008 1:40:38 PM | P | PASS |
|
|
Permit finaled
|
BLD07-01997
| FIRE-Final Inspection | 1/7/2008 | 1/8/2008 | 1/8/2008 12:15:05 PM | A | PASS |
|
|
Life safety passed.
|
FIR07-01046
| INSP-Sprinkler Rough-in/Hydro | 1/7/2008 | 1/8/2008 | 1/8/2008 11:23:54 AM | A | PASS |
|
|
The sprinkler piping is ok to cover. No pendant heads/arm-overs have been installed on the drop piping in the larger area. Hangers have been installed at the deck in this location.
|
FIR07-01011
| INSP-Final Inspection | 1/4/2008 | 1/8/2008 | 1/8/2008 10:55:05 AM | A | PASS |
|
|
Permit finaled
|