Inspections for the day of: Thursday, January 8, 2009.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00683 INSP-Final Inspection1/8/20091/8/20091/13/2009 5:30:45 PMPPASS
Okay for final per signed letter of compliance and testing verification provided by the state elevator inspection.
FIR06-00226 INSP-Sprinkler Rough-in/Hydro1/8/20091/8/20091/8/2009 4:55:35 PMPPART
UG fire supply line hydro test passed.
FIR06-00351 INSP-Sprinkler Rough-in/Hydro1/8/20091/8/20091/8/2009 4:54:40 PMPPART
UG hydrostatic test completed acceptable.
FIR08-00270 INSP-Conference1/8/20091/8/20091/8/2009 4:53:22 PMPDONE
Regarding FDC valves at the standpipes.
BLD08-02237 FIRE-Conference1/8/20091/8/20091/8/2009 4:50:15 PMPNH
Contact Paul
BLD08-01434 FIRE-Final Inspection1/8/20091/8/20091/8/2009 4:49:50 PMPFAIL
Missing one PFE, noted one exit sign to be repaired, need project related fire alarm final passed as well.
BLD08-01034 FIRE-Final Inspection1/8/20091/8/20091/8/2009 12:08:47 PMPNR
Chad- life safety Phone #: ###-#### Pending fire alarm permit final.
FIR08-00678 FIR-Aging Inspection1/8/20091/8/20091/8/2009 12:04:53 PM PEND
Pending site inspection request for work when complete.
FIR08-00018 INSP-Sprinkler Rough-in/Hydro1/6/20091/8/20091/8/2009 12:00:34 PMANR
10th Floor Cover - Contact: Jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
FIR08-00776 INSP-Alarm Testing1/7/20091/8/20091/8/2009 11:59:28 AMAPART
See approved plan set for locations of devices inspected and passed today including dampers, strobes, smoke detectors-noted one SD at the corridor address #58 to be relocated due to proximity to an HVAC diffuser, existing MP #101 tested okay.
FIR08-00018 INSP-Supply line flush1/6/20091/8/20091/8/2009 11:53:15 AMAPART
UG fire supply line flush completed satisfactory.
FIR08-00739 INSP-Alarm Testing1/6/20091/8/20091/8/2009 11:52:27 AMAFAIL
Notification appliances at the new tenant remodel area failed to function on battery power.
BLD08-01956 FIRE-Final Inspection1/7/20091/8/20091/8/2009 11:50:23 AMAPASS
Fire life safety passed, contractor to provide one additional fire extinguisher to be mounted as discussed-to be verified at structural final.