FIR08-00683
| INSP-Final Inspection | 1/8/2009 | 1/8/2009 | 1/13/2009 5:30:45 PM | P | PASS |
|
|
Okay for final per signed letter of compliance and testing verification provided by the state elevator inspection.
|
FIR06-00226
| INSP-Sprinkler Rough-in/Hydro | 1/8/2009 | 1/8/2009 | 1/8/2009 4:55:35 PM | P | PART |
|
|
UG fire supply line hydro test passed.
|
FIR06-00351
| INSP-Sprinkler Rough-in/Hydro | 1/8/2009 | 1/8/2009 | 1/8/2009 4:54:40 PM | P | PART |
|
|
UG hydrostatic test completed acceptable.
|
FIR08-00270
| INSP-Conference | 1/8/2009 | 1/8/2009 | 1/8/2009 4:53:22 PM | P | DONE |
|
|
Regarding FDC valves at the standpipes.
|
BLD08-02237
| FIRE-Conference | 1/8/2009 | 1/8/2009 | 1/8/2009 4:50:15 PM | P | NH |
|
|
Contact Paul
|
BLD08-01434
| FIRE-Final Inspection | 1/8/2009 | 1/8/2009 | 1/8/2009 4:49:50 PM | P | FAIL |
|
|
Missing one PFE, noted one exit sign to be repaired, need project related fire alarm final passed as well.
|
BLD08-01034
| FIRE-Final Inspection | 1/8/2009 | 1/8/2009 | 1/8/2009 12:08:47 PM | P | NR |
|
|
Chad- life safety Phone #: ###-#### Pending fire alarm permit final.
|
FIR08-00678
| FIR-Aging Inspection | 1/8/2009 | 1/8/2009 | 1/8/2009 12:04:53 PM | | PEND |
|
|
Pending site inspection request for work when complete.
|
FIR08-00018
| INSP-Sprinkler Rough-in/Hydro | 1/6/2009 | 1/8/2009 | 1/8/2009 12:00:34 PM | A | NR |
|
|
10th Floor Cover - Contact: Jeff Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
|
FIR08-00776
| INSP-Alarm Testing | 1/7/2009 | 1/8/2009 | 1/8/2009 11:59:28 AM | A | PART |
|
|
See approved plan set for locations of devices inspected and passed today including dampers, strobes, smoke detectors-noted one SD at the corridor address #58 to be relocated due to proximity to an HVAC diffuser, existing MP #101 tested okay.
|
FIR08-00018
| INSP-Supply line flush | 1/6/2009 | 1/8/2009 | 1/8/2009 11:53:15 AM | A | PART |
|
|
UG fire supply line flush completed satisfactory.
|
FIR08-00739
| INSP-Alarm Testing | 1/6/2009 | 1/8/2009 | 1/8/2009 11:52:27 AM | A | FAIL |
|
|
Notification appliances at the new tenant remodel area failed to function on battery power.
|
BLD08-01956
| FIRE-Final Inspection | 1/7/2009 | 1/8/2009 | 1/8/2009 11:50:23 AM | A | PASS |
|
|
Fire life safety passed, contractor to provide one additional fire extinguisher to be mounted as discussed-to be verified at structural final.
|