Inspections for the day of: Thursday, January 8, 2009.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-02470 FIRE-Final Inspection1/8/20091/8/20091/9/2009 4:01:09 PMPPASS
Life safety passed
FIR08-00526 INSP-Final Inspection1/6/20091/8/20091/8/2009 4:04:37 PMAPASS
Permit finaled.
FIR08-00704 INSP-Alarm Testing1/6/20091/8/20091/8/2009 4:00:25 PMAFAIL
See the city approved plans for locations of deficiencies which include all of the strobes in the storage areas being mounted too high, alot of the strobes over the main sales floor are overspaced off of the walls and the strobes in the deli area are overspaced. None of the audio/visual devices were tested for operation. As-built will be required showing any additional devices. The NAC panels have been tested for interconnection to the existing facp.
BLD08-01056 FIRE-Final Inspection1/7/20091/8/20091/8/2009 3:56:35 PMAPASS
Life safety passed.
FIR08-00520 INSP-Final Inspection1/7/20091/8/20091/8/2009 3:55:45 PMAFAIL
Lower the 110 cd strobe in the storage area, install the existing smoke detector that is over the facp to the deck, provide the missing strobe in the east storage area and retest all of the audio/visual devices.
FIR08-00632 INSP-Final Inspection1/7/20091/8/20091/8/2009 3:53:45 PMAFAIL
All of the initiating devices were tested today. Items needing corrected include providing separate points for the first floor flow switch and the second floor flow switch. The horn/strobes need to be tested for sync and all of the elevator functions need to be tested as well. Permit will not be finaled until Alarmco has submitted and passed inspection for their wireless transmitter. As-builts from Simplex are required showing the small modifications and the deletion of the phone lines.