Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00510 FIR-Aging Inspection1/8/20131/8/20131/9/2013 9:40:47 AM NR
wip
FIR12-00744 INSP-Final Inspection1/8/20131/8/20131/8/2013 3:48:09 PMPFAIL
The new 15cd strobe in the corridor is overspaced. Also notification needs to be extended into the corridor in front of the restrooms since the door that is shown on the building plans has not been installed. No testing was actually performed. All other spacing within the tenant space appears ok. Tim and I discussed options.
BLD12-02323 FIRE-Final Inspection1/7/20131/8/20131/8/2013 2:49:55 PMAPASS
Life safety passed.
BLD12-03228 FIRE-Final Inspection1/7/20131/8/20131/8/2013 9:31:10 AMAFAIL
Provide automatic flush bolts for the main exit inactive leaf or remove all hardware to meet the exception. Provide sticker at door. Provide fire extinguisher as discussed. Contact plan review to verify that only one restroom is needed since one of the two shown on the plans is missing.