Inspections for the day of: Wednesday, January 8, 2014.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-00044 Rough-In Permanent Service1/8/20141/8/20141/8/2014 2:54:43 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 314.20 boxes shall be flush with finished siding in combustible material, 314.23 shall protect nm cable within 6' of attic access, 334.30 shall secure nm cable within 12" of panel, BCC shall post address and job id sticker
ELE14-00038 Permanent Service1/8/20141/8/20141/8/2014 2:04:35 PMPPASS
jay Phone #: ###-#### corrections made, p/s o/h rec ok
ELE13-02856 Permanent Service1/6/20141/8/20141/8/2014 1:10:17 PMAPASS
call first Phone #: ###-#### >> Inspection requested via web by PAT MILLER p/s o/h rec ok
ELE13-00748 Electrical Rough-In1/8/20141/8/20141/8/2014 12:40:34 PMPPASS
josh - late afternoon please Phone #: ###-#### ri ok
ELE13-02358 Electrical Rough-In1/7/20141/8/20141/8/2014 10:32:50 AMAPASS
Office area Phone #: ###-#### >> Inspection requested via web by Bryan Atkins office walls only ok cover
ELE14-00014 Rough-In Permanent Service1/7/20141/8/20141/8/2014 10:10:33 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Bob Glenn called, left correction notice, NEC 300.14 shall provide 6" free conductor length, 110.14 shall properly install ground splicing connections
ELE13-02967 Final1/8/20141/8/20141/8/2014 9:46:55 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn ok final
ELE14-00033 Electrical Rough-In1/7/20141/8/20141/8/2014 9:13:07 AMAPASS
joe Phone #: ###-#### told owner to use # 12 wire to t'stat, ri ok
ELE14-00042 Final1/7/20141/8/20141/8/2014 8:38:27 AMAFAIL
Power off for over 1 year, Rear shed will be removed. Phone #: ###-#### >> Inspection requested via web by shane vigil called, shall bring grounding up to code, range and dryer re-wire to 4- wire if required, clean up shed wiring