ELE14-00044
| Rough-In Permanent Service | 1/8/2014 | 1/8/2014 | 1/8/2014 2:54:43 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, left correction notice, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 314.20 boxes shall be flush with finished siding in combustible material, 314.23 shall protect nm cable within 6' of attic access, 334.30 shall secure nm cable within 12" of panel, BCC shall post address and job id sticker
|
ELE14-00038
| Permanent Service | 1/8/2014 | 1/8/2014 | 1/8/2014 2:04:35 PM | P | PASS |
|
|
jay Phone #: ###-#### corrections made, p/s o/h rec ok
|
ELE13-02856
| Permanent Service | 1/6/2014 | 1/8/2014 | 1/8/2014 1:10:17 PM | A | PASS |
|
|
call first Phone #: ###-#### >> Inspection requested via web by PAT MILLER p/s o/h rec ok
|
ELE13-00748
| Electrical Rough-In | 1/8/2014 | 1/8/2014 | 1/8/2014 12:40:34 PM | P | PASS |
|
|
josh - late afternoon please Phone #: ###-#### ri ok
|
ELE13-02358
| Electrical Rough-In | 1/7/2014 | 1/8/2014 | 1/8/2014 10:32:50 AM | A | PASS |
|
|
Office area Phone #: ###-#### >> Inspection requested via web by Bryan Atkins office walls only ok cover
|
ELE14-00014
| Rough-In Permanent Service | 1/7/2014 | 1/8/2014 | 1/8/2014 10:10:33 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Bob Glenn called, left correction notice, NEC 300.14 shall provide 6" free conductor length, 110.14 shall properly install ground splicing connections
|
ELE13-02967
| Final | 1/8/2014 | 1/8/2014 | 1/8/2014 9:46:55 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn ok final
|
ELE14-00033
| Electrical Rough-In | 1/7/2014 | 1/8/2014 | 1/8/2014 9:13:07 AM | A | PASS |
|
|
joe Phone #: ###-#### told owner to use # 12 wire to t'stat, ri ok
|
ELE14-00042
| Final | 1/7/2014 | 1/8/2014 | 1/8/2014 8:38:27 AM | A | FAIL |
|
|
Power off for over 1 year, Rear shed will be removed. Phone #: ###-#### >> Inspection requested via web by shane vigil called, shall bring grounding up to code, range and dryer re-wire to 4- wire if required, clean up shed wiring
|