Inspections for the day of: Thursday, January 8, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorCevyn Recla
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-02598 Final1/7/20151/8/20151/8/2015 2:02:27 PMPPASS
Paul. After 1:30. Code #11405. Phone #: ###-#### Inspection requested via web by Sean DeLacy
corrections made, final OK
ELE15-00010 Rough-In Permanent Service1/8/20151/8/20151/8/2015 1:41:35 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov
UFER is in crawl space under meter, check wires in crawl for staples on trim,
RI OK, PS, UG, N, OK
ELE13-01804 Final1/8/20151/8/20151/8/2015 1:01:55 PMPNR
Contact: Brian Gee Phone #: ###-#### Inspection requested via web by Deb Gooden
Unable to open box due to vandalism, the contractor will repair and call back in,
ELE15-00050 Electrical Rough-In1/8/20151/8/20151/8/2015 12:38:22 PMPPASS
Please call Eddy at ###-####. So I can get you in Phone #: ###-#### Inspection requested via web by Eddy Udry
2 office, 1 bath, walls and ceiling
RI OK to cover
ELE14-03520 Final1/8/20151/8/20151/8/2015 11:49:57 AMPDONE
Ron Phone #: ###-####
corrections made, final OK
ELE12-00377 ELE-Aging Inspection1/8/20151/8/20151/8/2015 11:27:41 AM DONE
Building is completed, all units are occupied, permit is open, and TDR has stated that he never finished his work. Someone else has completed the electrical work, and owner has rented out with no inspection.
ELE12-02025 ELE-Aging Inspection1/8/20151/8/20151/8/2015 11:06:23 AM DONE
see final
ELE12-02025 Final1/8/20151/8/20151/8/2015 11:06:10 AMPPASS
UL listing, final OK
ELE14-02652 Final1/7/20151/8/20151/8/2015 11:01:07 AMAFAIL
Please call Cory if you have any questions. ###-####
thanks, Phone #: ###-#### Inspection requested via web by Cyndi Dale
called contractor
210.8.A.7 GFCI protection required, outlets within six feet of edge of sink
314.25, completed installations shall have a cover, hallway ceiling box.
ELE14-02914 Final1/7/20151/8/20151/8/2015 10:30:08 AMAPASS
if you have access issues please give me a call. Thanks ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan
Final OK
ELE15-00035 Rough-In Permanent Service1/8/20151/8/20151/8/2015 9:55:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson
RI OK, PS, UG, N, OK
ELE15-00006 Conference1/7/20151/8/20151/8/2015 8:59:53 AMADONE
Jeff Phone #: ###-####
discussed kitchen remodel, support and securing of wire, any junction boxes need to be accessible, wire gauges, adding of light outlets.
ELE15-00045 Rough-In Permanent Service1/7/20151/8/20151/7/2015 1:34:03 PMADONE
inspection on walls only, adjacent unit Phone #: ###-#### Inspection requested via web by David Nelson
Rough in Walls ok, see pmt. 15-00034