ELE15-03715
| Final | 1/8/2016 | 1/8/2016 | 1/8/2016 2:40:59 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson Final ok
|
ELE15-03760
| Electrical Rough-In | 1/7/2016 | 1/8/2016 | 1/8/2016 2:00:26 PM | P | PASS |
|
|
Contact: Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Listing confirmed. Rough in ok
|
ELE15-03874
| Final | 1/8/2016 | 1/8/2016 | 1/8/2016 1:23:17 PM | P | PASS |
|
|
Super indent will open it up he will be there in about 30 mins Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
|
ELE15-04088
| Final | 1/8/2016 | 1/8/2016 | 1/8/2016 12:31:00 PM | P | PASS |
|
|
Paul. Early as possible. Phone #: ###-#### Inspection requested via web by Sean DeLacy Final ok
|
ELE15-03796
| Final | 1/7/2016 | 1/8/2016 | 1/8/2016 11:40:22 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Celinda Winters All GFCI devices located in panel. Final ok
|
ELE16-00032
| Final | 1/7/2016 | 1/8/2016 | 1/8/2016 10:55:53 AM | A | PASS |
|
|
Walk in cooler only Phone #: ###-#### Inspection requested via web by Warren Fry Print on sight shows tenant will have access to over current devices. Final ok
|
ELE16-00017
| Conference | 1/8/2016 | 1/8/2016 | 1/8/2016 10:20:36 AM | P | DONE |
|
|
Owner called discussed the cooktop wiring . As per manufacurers instructions only 3 wire connection required due to a neutral not provide from factory. Cooktop frame will be bonded with an equpment grounding conductor.
|
ELE16-00047
| Conference | 1/7/2016 | 1/8/2016 | 1/8/2016 9:52:14 AM | A | DONE |
|
|
Michael Phone #: ###-#### Owner called, will not be able to meet on sight so discussed over phone installation of circuit for jetted tub. He will install dedicated circuit, GFCI to be located in hall way near bathroom and install receptacle under tub for pump and heater to plug into.
|
ELE15-03715
| Final | 1/7/2016 | 1/8/2016 | 1/8/2016 9:24:07 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson 406.9(A)- All 15 and 20 amp receptacle outlets installed outdoors shall be weather resistant type. Called mail box is full cannot accept new messages. Left correction notice
|
ELE15-03874
| Final | 1/7/2016 | 1/8/2016 | 1/8/2016 8:55:54 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe No access door code not working
|