Inspections for the day of: Friday, January 8, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-03715 Final1/8/20161/8/20161/8/2016 2:40:59 PMPPASS
Phone #: ###-#### Inspection requested via web by David Nelson Final ok
ELE15-03760 Electrical Rough-In1/7/20161/8/20161/8/2016 2:00:26 PMPPASS
Contact: Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher
Listing confirmed. Rough in ok
ELE15-03874 Final1/8/20161/8/20161/8/2016 1:23:17 PMPPASS
Super indent will open it up he will be there in about 30 mins Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
ELE15-04088 Final1/8/20161/8/20161/8/2016 12:31:00 PMPPASS
Paul. Early as possible. Phone #: ###-#### Inspection requested via web by Sean DeLacy Final ok
ELE15-03796 Final1/7/20161/8/20161/8/2016 11:40:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Celinda Winters
All GFCI devices located in panel. Final ok
ELE16-00032 Final1/7/20161/8/20161/8/2016 10:55:53 AMAPASS
Walk in cooler only Phone #: ###-#### Inspection requested via web by Warren Fry
Print on sight shows tenant will have access to over current devices.
Final ok
ELE16-00017 Conference1/8/20161/8/20161/8/2016 10:20:36 AMPDONE
Owner called discussed the cooktop wiring . As per manufacurers instructions only 3 wire connection required due to a neutral not provide from factory. Cooktop frame will be bonded with an equpment grounding conductor.
ELE16-00047 Conference1/7/20161/8/20161/8/2016 9:52:14 AMADONE
Michael Phone #: ###-####
Owner called, will not be able to meet on sight so discussed over phone installation of circuit for jetted tub. He will install dedicated circuit, GFCI to be located in hall way near bathroom and install receptacle under tub for pump and heater to plug into.
ELE15-03715 Final1/7/20161/8/20161/8/2016 9:24:07 AMAFAIL
Phone #: ###-#### Inspection requested via web by David Nelson
406.9(A)- All 15 and 20 amp receptacle outlets installed outdoors shall be weather resistant type.
Called mail box is full cannot accept new messages. Left correction notice
ELE15-03874 Final1/7/20161/8/20161/8/2016 8:55:54 AMAFAIL
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
No access door code not working