Inspections for the day of: Friday, January 8, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02607 Final1/8/20161/8/20161/8/2016 2:13:26 PMPPASS
Mitch Phone #: ###-#### final ok
ELE15-04054 Electrical Rough-In1/8/20161/8/20161/8/2016 1:58:07 PMPPASS
Phone #: ###-#### Inspection requested via web by Jim Williams contractor will replace breaker feeding sub panel to a 100 amp as per 310.16 rough-in ok cover
ELE16-00057 Temporary Service1/8/20161/8/20161/8/2016 1:20:59 PMPPASS
Phone #: ###-#### Inspection requested via web by Don Conley t/s u/g n ok
ELE15-03274 Final1/8/20161/8/20161/8/2016 12:35:08 PMPFAIL
Justin Phone #: ###-#### 210.8 (b) (5) receptacles located with 6' of a sink shall have GFCI protection
ELE16-00056 Rough-In Permanent Service1/8/20161/8/20161/8/2016 11:39:04 AMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI rough-in ok cover p/s u/g n ok
ELE15-03368 Final1/7/20161/8/20161/8/2016 11:13:03 AMAPASS
Phone #: ###-#### Inspection requested via web by Brandon Hillman final ok
ELE15-03269 Final1/7/20161/8/20161/8/2016 10:32:52 AMAPASS
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson final ok
ELE16-00016 Permanent Service1/7/20161/8/20161/8/2016 10:20:45 AMAPASS
Phone #: ###-#### Inspection requested via web by Kendra Lanham needed rough-in and p/s
ELE16-00016 Rough-In Permanent Service1/8/20161/8/20161/8/2016 10:20:24 AMPPASS
Phone #: ###-#### Inspection requested via web by Kendra Lanham contractor will add funds to permit for rough-in. underground ok cover p/s o/h rec ok
ELE15-03662 Final1/7/20161/8/20161/8/2016 9:30:38 AMAFAIL
Jeff Phone #: ###-#### section 4-05-32 boise city ordinance wiring ith close proximityhall be in accordinance with present code(blanks required in open boxes in floor as well
ELE15-03735 Electrical Rough-In1/7/20161/8/20161/8/2016 8:49:47 AMAPASS
Contact: Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher verfied ul listing and power supply rough-in sign ok