PLM17-03463
| Final | 1/8/2018 | 1/8/2018 | 1/8/2018 4:54:32 PM | P | PASS |
|
|
Can you call Bryan with Lexar Homes please he can be there in 15 min. Thanks Sem Phone #: ###-#### Inspection requested via web by Semsudin Konjuhovac
|
PLM18-00050
| Final | 1/4/2018 | 1/8/2018 | 1/8/2018 4:21:52 PM | P | PASS |
|
|
Please call homeowner 30 minutes in advance for access at ###-#### and call Eddie with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Lea Briggs
|
PLM17-03716
| Plumbing Rough-in | 1/8/2018 | 1/8/2018 | 1/8/2018 4:04:52 PM | P | FAIL |
|
|
Mike Phone #: ###-####. Santees cannot be installed on their back. Install wye branch fittings on the horizontal.
|
PLM17-04533
| Final | 1/4/2018 | 1/8/2018 | 1/8/2018 3:22:40 PM | P | FAIL |
|
|
Lock box code 0726 Phone #: ###-#### Inspection requested via web by Ryan Baker. 1. The dishwasher drain must rise to the highest point in the cabinet. 2.. Only one slip-joint is allowed on the outlet side of the weir. 3. Pipe the water heater t&p outside of the closure. 4. Each flue joint on the water heater must have 3 screws. 5. Add a 3" drip leg to the water heater gas feed.
|
PLM18-00078
| Plumbing Rough-in | 1/8/2018 | 1/8/2018 | 1/8/2018 2:59:52 PM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Raul Castanon 1. the water softener drain must be 3/4 2. Add a 3" cleanout above the floor for the powder bath. 3. Add a cleanout to the back to back lavatories at the pool bath.
|
PLM17-04374
| DOC - Permit Finaled | 1/8/2018 | 1/8/2018 | 1/8/2018 2:32:04 PM | P | PASS |
|
|
|
PLM16-04144
| Final | 1/8/2018 | 1/8/2018 | 1/8/2018 2:28:36 PM | P | PART |
|
|
Bldg 300 complete with the expecption of the corroction notice to add a rp to the dishwasher.
|
PLM17-01748
| Final | 1/5/2018 | 1/8/2018 | 1/8/2018 9:32:56 AM | A | FAIL |
|
|
Key in electrical outlet west wall Phone #: ###-#### Inspection requested via web by Jeff Coate. Pex cannot be within 18" of the water heater on the hot and cold connections. Use copper.
Trap seal exceeds 4". Look at a LA pattern trap with a trap adapter. The sink will adjust up at the bottom of the legs.
|
PLM17-05070
| Water and/or Sewer | 1/5/2018 | 1/8/2018 | 1/8/2018 9:14:39 AM | A | PART |
|
|
PLEASE INSPECT THE WATER LINE ONLY Phone #: ###-#### Inspection requested via web by Darren Wood. Water service ok to cover
|
PLM17-04815
| Water and/or Sewer | 1/5/2018 | 1/8/2018 | 1/8/2018 8:56:24 AM | A | PART |
|
|
Please accommodate an 8 o''clock inspection Phone #: ###-#### Inspection requested via web by David Scaggs. Water service ok to cover
|