Inspections for the day of: Monday, January 8, 2018.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00730 INSP-Sprinkler Rough-in/Hydro1/8/20181/8/20181/8/2018 3:23:21 PMPDONE
Hydrostatic test witnessed for overhead fire sprinkler piping on levels 1 and 2, no loss of pressure observed at riser gauge.
FIR17-00730 INSP-Sprinkler Rough-in/Hydro1/8/20181/8/20181/8/2018 3:21:14 PMPPASS
Rough to cover inspection for levels 2 and 3 for overhead fire sprinkler piping complete, approved for cover.
FIR17-00726 INSP-Sprinkler Rough-in1/8/20181/8/20181/8/2018 3:19:15 PMPCANC
Inspection request will be rescheduled for 9JAN2018, this request is cancelled.
BLD16-02431 FIRE-Final Inspection1/5/20181/8/20181/8/2018 12:24:47 PMAPASS
Final life fire safety inspection complete.
FIR17-00173 INSP-Final Inspection1/8/20181/8/20181/8/2018 12:00:26 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
BLD17-04301 FIRE-Final Inspection1/5/20181/8/20181/8/2018 11:36:15 AMAPASS
Life fire safety inspection for area of work complete.
BLD17-04385 FIRE-Final Inspection1/5/20181/8/20181/8/2018 11:07:23 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for area of work complete.
FIR17-00647 INSP-Sprinkler Rough-in1/5/20181/8/20181/8/2018 10:54:52 AMAPART
Rough to cover inspection for overhead fire sprinkler piping above hardlids complete, hardlids approved for cover.
FIR17-00657 INSP-Sprinkler Rough-in1/8/20181/8/20181/8/2018 10:41:21 AMPPASS
Rough to ocver inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
FIR17-00212 INSP-Final Inspection1/5/20181/8/20181/8/2018 10:40:44 AMADONE
Underground flush complete.
BLD16-02410 FIRE-Final Inspection1/5/20181/8/20181/8/2018 10:19:21 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags, knox box is located by the fire sprinkler riser room. Final life fire safety inspection complete.
FIR18-00008 INSP-Final Inspection1/5/20181/8/20181/8/2018 10:18:08 AMAPASS
Final fire alarm inspection complete.
FIR16-00795 INSP-Final Inspection1/4/20181/8/20181/8/2018 10:17:39 AMAPASS
Final fire sprinkler inspection complete.
FIR17-00678 INSP-Final Inspection1/5/20181/8/20181/8/2018 8:25:28 AMAPASS
Final fire sprinkler inspection for area of work complete.
FIR17-00678 INSP-Sprinkler Rough-in/Hydro1/5/20181/8/20181/8/2018 8:25:01 AMAPASS
Rough in inspection complete.
FIR17-00703 INSP-Sprinkler Rough-in1/5/20181/8/20181/8/2018 8:24:38 AMAPASS
Final fire sprinkler inspection for area of work complete.