FIR18-00750
| INSP-Final Inspection | 1/8/2019 | 1/8/2019 | 1/8/2019 3:22:58 PM | P | PASS |
|
|
Troubles on fire alarm panel have been repaired/cleared, final fire alarm inspection complete.
|
FIR18-00777
| INSP-Final Inspection | 1/4/2019 | 1/8/2019 | 1/8/2019 3:14:19 PM | P | PASS |
|
|
Final fire alarm inspection for scope of work complete.
Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
FIR18-00718
| INSP-Final Inspection | 1/4/2019 | 1/8/2019 | 1/8/2019 3:13:35 PM | P | FAIL |
|
|
Flow switches on levels 1 and 2 go instantly to alarm with water flow, flow switches will need to be replaced. Basement level flow switch would not trip with a consistant time, recommend replacement of switch for basement level. PIV took 12 turns to report to panel, needs to be 2 1/2 turns or less.
Please call chris ford Phone #: ###-#### Inspection requested via web by Jessia Maxwell
|
FIR18-00942
| INSP-Sprinkler Rough-in/Hydro | 1/8/2019 | 1/8/2019 | 1/8/2019 3:10:26 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at city static pressure.
|
FIR18-00942
| INSP-Sprinkler Rough-in/Hydro | 1/7/2019 | 1/8/2019 | 1/8/2019 3:08:22 PM | A | PART |
|
|
Rough in inspection for overhead fire sprinkler piping complete, areas between conditioned spaces approved for cover, tenting to be installed on attic piping at a later date, areas requiring tenting not approved for cover.
Please call Anthony before heading out, thank you! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00687
| INSP-Final Inspection | 1/8/2019 | 1/8/2019 | 1/8/2019 2:37:30 PM | P | CANC |
|
|
Please call ahead Phone #: ###-#### >> Inspection requested via web by Gary Gambino Inspection cancelled from web by: Gary Gambino
|
FIR18-00834
| INSP-Sprinkler Rough-in | 1/8/2019 | 1/8/2019 | 1/8/2019 12:05:50 PM | P | PART |
|
|
Rough to cover ins[pection for IBR complete, IBR approved for cover, remaining underground supply to be installed at a later date.
Bryan Collins is the contact for this underground RTC inspection. Thank you for your help. Have a nice day. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00725
| INSP-Sprinkler Rough-in | 1/7/2019 | 1/8/2019 | 1/8/2019 11:52:58 AM | A | PASS |
|
|
Rough to cover inspection for overehad fire sprinkler piping in area of work complete, approved for cover.
Please call Randy if there are any questions. Thanks. Phone #: ###-#### Inspection requested via web by Jeff Packham
|
FIR18-00491
| INSP-Final Inspection | 1/7/2019 | 1/8/2019 | 1/8/2019 11:52:17 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
Call Anthony before heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR18-00731
| INSP-Final Inspection | 1/7/2019 | 1/8/2019 | 1/8/2019 11:51:45 AM | A | PASS |
|
|
Final fire sprinkler inspection complete.
Call Anthony when heading out, thanks! Phone #: ###-#### Inspection requested via web by Anthony Minichiello
|
FIR17-00474
| INSP-Supply line flush | 1/7/2019 | 1/8/2019 | 1/8/2019 11:48:27 AM | A | DONE |
|
|
Underground main line flush complete.
Jeff Chaney is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
FIR18-00021
| INSP-Sprinkler Rough-in/Hydro | 1/7/2019 | 1/8/2019 | 1/8/2019 9:33:58 AM | A | CANC |
|
|
Cancelled per conversation woith point of contact.
200lb hydro. George is the contact. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-04530
| FIRE-Final Inspection | 1/7/2019 | 1/8/2019 | 1/8/2019 9:01:08 AM | A | FAIL |
|
|
Provide exit signs as shown on city approved drawings. Fire extinguisher on east side of building needs to be inspected and tagged, last inspection was 2011. Provide sticker on main entry reading "Door to remain unlocked while building is occupied". Designated exit on the east side of tenant space is blocked by golf cart, designated exits need to be clear for egress.
Tim Phone #: ###-####
|
FIR18-00021
| INSP-Sprinkler Rough-in | 1/7/2019 | 1/8/2019 | 1/8/2019 8:41:18 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete, approved for cover.
overhead RTC. Phone #: ###-#### Inspection requested via web by Stan Beus
|
BLD18-04124
| FIRE-Final Inspection | 1/7/2019 | 1/8/2019 | 1/8/2019 8:15:38 AM | A | CANC |
|
|
Area of work not ready for life fire safety inspection, treated this as a conference, fire alarm modifications will be required.
Antonio Phone #: ###-####
|
FIR19-00002
| INSP-Final Inspection | 1/8/2019 | 1/8/2019 | 1/8/2019 7:33:18 AM | A | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
BLD18-01906
| FIRE-Final Inspection | 1/8/2019 | 1/8/2019 | 1/8/2019 7:31:43 AM | A | PASS |
|
|
Troubles on fire panel have been repaired, final life fire safety inspection complete.
Phone #: ###-#### Inspection requested via web by Jason Ginn
|
FIR18-00723
| INSP-Final Inspection | 1/3/2019 | 1/8/2019 | 1/8/2019 7:30:57 AM | A | PASS |
|
|
Previously noted items have been repaired, final fire alarm inspection complete.
7am inspection coordinated with Jim Paige Phone #: ###-#### Inspection requested via web by Shane Lesteberg
|
BLD17-01000
| FIRE-Conference | 1/3/2019 | 1/8/2019 | 1/8/2019 12:00:00 AM | A | DONE |
|
|
Temp C of O request- See Ron Hill to schedule plan Request 10 AM with all inspectors if possible - Bruce Phone #: ###-####
|