Inspections for the day of: Thursday, January 9, 2003.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS02-00179 FIR-Final1/8/20031/9/20031/10/2003 12:00:00 AMAFAIL
Showed up on aging...looks like reinspection needed. Carl talked to two people inside about fixing the exit signs and annual inspections for the extinguisher; they said they could have it ready next week 1/10/2003 10:49:20 AM
FIR02-00331 FIR-Aging Inspection1/9/20031/9/20031/9/2003 12:00:00 AM NR
talked to Alarmco and they will schedule for next week 1/9/2003 12:30:20 PM
FIR02-00507 INSP-Sprinkler Rough-in/Hydro1/8/20031/9/20031/9/2003 12:00:00 AMAFAIL
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie r/i inspection okay; need tenting and approval prior to cover; riser not complete 1/9/2003 9:32:20 AM
BLD02-02267 FIRE-Sprinkler Rough-in1/9/20031/9/20031/9/2003 12:00:00 AMAFAIL
need tenting and approval prior to cover
FIR02-00455 INSP-Sprinkler Rough-in1/9/20031/9/20031/9/2003 12:00:00 AMPFAIL
need retaining straps on all beam clamps
BLD02-02920 FIRE-Final Inspection1/9/20031/9/20031/9/2003 12:00:00 AMPPASS
-tim; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie signed for Jim Storey also per his approval 1/9/2003 1:44:04 PM
BLD02-02432 FIRE-Final Inspection1/9/20031/9/20031/9/2003 12:00:00 AMPFAIL
DAVE; Phone #: ###-#### Internet Inspection Request from: Darla Downs not a final inspection but a sprinkler r/i; need retaining straps on all beam clamps 1/9/2003 2:56:33 PM
FIR02-00338 INSP-Sprinkler Rough-in/Hydro1/9/20031/9/20031/9/2003 12:00:00 AMPPART
above grnd. ###-#### above ground hydro okay 1/9/2003 1:17:06 PM
FIR02-00490 INSP-Final Inspection1/8/20031/9/20031/9/2003 12:00:00 AMPFAIL
###-#### need to complete permit FIR02-00331 first; reviewed placement of all devices/NAC circuits and will need as builts for the minor changes on the NAC's; need labels at FACP for new zones; fire sprinkler overdue inspection;
1/9/2003 4:51:20 PM