BLD03-01377
| FIRE-Final Inspection | 1/8/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | A | FAIL |
|
|
need alarm reports and could not test elevators 1/9/2004 10:31:52 AM
|
FIR03-00529
| INSP-Final Inspection | 1/8/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | A | CANC |
|
|
duplicate inspection 1/9/2004 10:49:13 AM
|
BLD03-02988
| FIRE-Final Inspection | 1/8/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | A | PASS |
|
|
Fire life safety finaled 1/9/2004 10:56:20 AM
|
FIR03-00367
| INSP-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | A | PASS |
|
|
Underground finaled
|
FIR03-00529
| INSP-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | A | PASS |
|
|
fire sprinklers finaled
|
FIR03-00569
| INSP-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given until the fire alarm plans have been resubmitted showing the access control connected to the fire alarm. All other fire alarm devices have been tested
|
BLD03-01107
| FIRE-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | A | PART |
|
|
A temporary occupancy was given until the fire alarm plans have been resubmitted showing the access control connected to the fire alarm. All other fire alarm devices have been tested. Fire life safety items are ok. I notified the contractor that painting the curbing for fire dept access will become an issue when the next building is built.
|
BLD03-01638
| FIRE-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | P | PASS |
|
|
fire life safety finaled 1/9/2004 3:29:39 PM
|
FIR03-00697
| INSP-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | P | PASS |
|
|
Fire alarm system finaled
|
BLD03-01377
| FIRE-Final Inspection | 1/9/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | P | PASS |
|
|
Fire life safety, fire alarm and fire sprinkler are finaled 1/9/2004 2:18:15 PM
|
FIR03-00692
| INSP-Sprinkler Rough-in/Hydro | 1/7/2004 | 1/9/2004 | 1/9/2004 12:00:00 AM | P | FAIL |
|
|
Inspection was for the entry area and the two restrooms. The hangers in the entry area need to be attached to the top of the structure and the pendants exceed 3' vertically from the peak. The upright sprinkler heads over both of the restrooms are overspaced and will require additional upright coverage 1/9/2004 2:08:16 PM
|
FIR03-00658
| INSP-Alarm Testing | 1/7/2004 | 1/9/2004 | 1/7/2004 2:36:47 PM | P | CANC |
|
|
Let me know what time would work for you to come out so that I can coordinate with the sprinkler fitters to be there too. Thanks Rick; Phone #: ###-#### Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
|